Plan Review Notes
Plan Review Notes For Permit 06040623
Permit Number 06040623
Review Stop E
Sequence Number 4
Notes
Date Text
2007-05-16 10:25:42** UNSAT**
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE PLANS ARE NOT INDICATING ANY
 REVISIONS BY CLOUDS/TRIANGLES OR DATES IN TITLE BLOCK.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THE PLANS ARE NOT DATED BY THE
 DESIGNER OF RECORD AS REQUIRED UNDER PER FS 481.221.
  
 3) NOTE: PLEASE SEE THE RISER DIAGRAM IS NOW REVISED
 SHOWING NO MAIN, YET PLANS STILL INDICATE A MAIN
 DISCONNECT OUTSIDE?
 PLEASE CLARIFY AND KNOW THAT NO MORE THAN 8FT OF
 UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE BUILDING.
 230.70.
  
 4) NOTE: PLEASE SEE 250.6, 250.24 AS EQUIPMENT
 GROUNDING CONDUCTORS ARE BEING BEFORE THE FIRST MEANS
 OF DISCONNECT AS THE RISER DOES NOT INDICATE ANY MAIN
 BEFORE THE PANEL?
 * EQUIPMENT GROUNDS ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT*
  
 5) NOTE: PLEASE SEE THE PLANS HAVE BEEN REVISED
 REMOVING THE PREVIOUS BATHS 2 AND 3, HOWEVER THE NEW
 PLANS INDICATE ONLY ONE BATH AND RECEPTACLE AS
 EXISTING. HOW IS THIS RECEPTACLE EXISTING WHEN THE
 WALLS/LAYOUT/ AND BATH IS NEW. PLEASE SEE PREVIOUS
 PLANS WHICH DID NOT INDICATE THIS.
 PLEASE COORDINATE AND CLARIFY THIS.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DETECTION DEVICES. IF THESE ARE 120V DEVICES WHICH
 DETECT AND SOUND AN ALARM, THEY ARE SMOKE ALARMS AND
 SHOULD BE SHOWN AS SA. IF THESE ARE INDEED SMOKE
 DETECTORS WHICH ARE SHOWN AS SD, THEN THESE ONLY DETECT
 AND PLANS NEED TO SHOW SOUNDING DEVICES AND PANEL FOR
 CONTROL.
  
 7) NOTE: PLEASE SEE PREVIOUS ISSUED PLANS REDLINED THE
 REQUIRED CODE FOR PLANS.
 PLEASE BE SURE THE FOLLOWING CODES ARE LISTED ON
 ELECTRICAL PLANS.
 2004 FBC, 2002 NFPA-70 (NEC) AND THE 2002 NFPA-72.
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]