| Plan Review Notes For Permit 06040623 |
| Permit Number |
06040623 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-24 00:00:00 | ***** REDLINED PLANS. | | | | | | | | | 1)PLEASE SEE MINIMUM CONDUIT SIZE SHALL | | | BE 2" FOR THE SEC'S AND THE FEEDERS FROM | | | MAIN DISCONNECT TO SUB PANEL. | | | PLEASE SEE CHAPTER 9,TABLES. | | | | | | 2) PLEASE SEE REDLINED NFPA-72 2002, | | | NFPA-70 2002 ON ELECTRICAL PLANS. | | | | | | 3) PLEASE SEE REDLINED MIN CLEARENCES | | | FOR THE AHU DISCONNECT AS SHOWN. | | | 110.26 | | | | | | | | | ** PLEASE REVISE NOTE #1 WHEN REVISING | | | PLANS BEFORE ROUGH ALONG WITH ANY OTHER | | | REVISIONS. |
|