2006-08-24 00:00:00***** REDLINED PLANS.
  
  
 1)PLEASE SEE MINIMUM CONDUIT SIZE SHALL
 BE 2" FOR THE SEC'S AND THE FEEDERS FROM
 MAIN DISCONNECT TO SUB PANEL.
 PLEASE SEE CHAPTER 9,TABLES.
  
 2) PLEASE SEE REDLINED NFPA-72 2002,
 NFPA-70 2002 ON ELECTRICAL PLANS.
  
 3) PLEASE SEE REDLINED MIN CLEARENCES
 FOR THE AHU DISCONNECT AS SHOWN.
 110.26
  
  
 ** PLEASE REVISE NOTE #1 WHEN REVISING
 PLANS BEFORE ROUGH ALONG WITH ANY OTHER
 REVISIONS.