Plan Review Notes
Plan Review Notes For Permit 06040623
Permit Number 06040623
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-23 00:00:00******** UNSAT 2ND REVIEW *********
  
 ** IMPORTANT **
 ONCE ALL REVIEWS ARE COMPLETE PLANS WILL
 BE PICKED UP FOR CORRECTIONS.
 BEFORE RESUBMITTING PLANS, PLEASE
 COMPLETELY "REMOVE" ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY "INSERT NEW"
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STMAPING. ONLY ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE SEPARATELY.
 THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 *************************************
  
 1) NOTE: PLEASE CORRELATE RISER AND
 PANEL, PLEASE SEE ONE SHOWS 200A AND THE
 OTHER 150A.
 106.1.2 FBC
  
 2) NOTE: PLEASE SEE LOCATIONS FOR
 FAN/LTS IN BEDRMS AND LIVING RMS ARE
 BEING SHOWN AS A "J" BOX ONLY. PLEASE
 CLARIFY AS FIXTURES OF SOME SORT IS
 REQUIRED FOR EGRESS LTS.
 210.70 LS 101 7.8
  
 3) NOTE: PLEASE SEE COVER SHEET SHOWS
 2000 LS 101, PLEASE KNOW, AS OF JAN 05,
 THE STATE ADOPTED THE 2003 LS 101.
 PLEASE ALSO PLACE THE FOLLOWIGN CODES ON
 THE ELECTRICAL PLANS AS REQUIRED.
 2002 NFPA-70, 2002 NFPA-72
  
 4) NOTE: PLEASE INDICATE THE REQUIRED
 LICENSE INFORMATION FOR MARK ROBINSON
 DESIGN , LLC.
 PLEASE SEE FS 481.219, FS 471.023 FOR
 MISSING CERTIFICATE OF AUTHORIZATION #.
 WHAT TYOE OF BUSINESS IS THIS? IF
 ARCHITECT WORKS FOR THIS DESIGN FIRM,
 PLEASE INCLUDECA #.
 61G1-16.004
  
 5) NOTE: PLEASE SEE MAX OCP FOR AHU IS
 TYPICALL 150% , HOWEVER PANEL SCHEDULE
 SHOWS 60A OCP FOR 5KW HEAT IN AHU?
 PLEASE SEE 424.3B FOR MIN @125%.
 PLEASE ALSO SEE #6, SHOWN WHICH IS OK,
 HOWEVER IF SHOWN ON PLANS, #6 WILL BE
 REQUIRED. PLEASE ALSO KNOW, IF THE 5KW
 UNTI CONTAINS THE TYPICAL 30A OCP, #6
 WILL NOT INSERT INTO A 30A BRKR.
 PLEASE ADJUST.
 106.1.2
  
 6) NOTE: PLEASE SEE 250.50, AS THE NEW
 "FOOTER STEEL" SHALL BE PART OF THE
 GROUNDING ELECTRODE SYSTEM.
 PLEASE ALSO CLARIFY THE "STRUCTURAL
 STEEL" AS NOTED.??
  
 7) NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCES FOR THE CU/ AHU DISC'S.
  
 8) NOTE: PLEASE SEE MISSING GFI RECEPTS
 FOR CU'S. (BOTH)
 210.63, 210.8A3
  
 9) NOTE: PLEASE VERIFY CIRCUITING OF LT
 OUTSIDE BATH #3, AS LTS IN THE SAME SW
 BOX ARE ON 19, HOWEVER LT FOR THE LT
 ADJACENT IS ON THE MASTER BEDRM/EXT
 RECEPT CIRCUIT. THIS IS OK, HOWEVER IF
 SHOWN, THIS IS REQUIRED. THIS IS ONLY
 NOTED FOR INFORMATIONAL PURPOSE AND THIS
 DOES NOT REQUIRE CHANGE.
 THIS CAN BE REVISED AT A LATER DATE, AS
 OTHER REVISIONS WILL MOST LIKELY TAKE
 PLACE.
  
 10) NOTE: PLEASE SEE SOME ELECTRICAL
 DEVICES ON PLANS ARE MISSING CIRCUITING.
 408.4.
  
 11) NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PLEASE SEE ARC FAULT IS ONLY
 SHWON FOR THE SD/LTS CIRCUIT AND ARC
 FUALT IS ONLY NOTED ON PLANS FOR RECEPTS
 NOT ALL AS REQUIRED PER 2002 NEC 210.12B
 PLEASE LIST ON SCHEDULE. 408.4.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  