| Date |
Text |
| 2006-07-23 00:00:00 | ******** UNSAT 2ND REVIEW ********* |
| | |
| | ** IMPORTANT ** |
| | ONCE ALL REVIEWS ARE COMPLETE PLANS WILL |
| | BE PICKED UP FOR CORRECTIONS. |
| | BEFORE RESUBMITTING PLANS, PLEASE |
| | COMPLETELY "REMOVE" ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY "INSERT NEW" |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STMAPING. ONLY ONE COPY OF THE |
| | OLD/VOIDED REMOVED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE SEPARATELY. |
| | THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | ************************************* |
| | |
| | 1) NOTE: PLEASE CORRELATE RISER AND |
| | PANEL, PLEASE SEE ONE SHOWS 200A AND THE |
| | OTHER 150A. |
| | 106.1.2 FBC |
| | |
| | 2) NOTE: PLEASE SEE LOCATIONS FOR |
| | FAN/LTS IN BEDRMS AND LIVING RMS ARE |
| | BEING SHOWN AS A "J" BOX ONLY. PLEASE |
| | CLARIFY AS FIXTURES OF SOME SORT IS |
| | REQUIRED FOR EGRESS LTS. |
| | 210.70 LS 101 7.8 |
| | |
| | 3) NOTE: PLEASE SEE COVER SHEET SHOWS |
| | 2000 LS 101, PLEASE KNOW, AS OF JAN 05, |
| | THE STATE ADOPTED THE 2003 LS 101. |
| | PLEASE ALSO PLACE THE FOLLOWIGN CODES ON |
| | THE ELECTRICAL PLANS AS REQUIRED. |
| | 2002 NFPA-70, 2002 NFPA-72 |
| | |
| | 4) NOTE: PLEASE INDICATE THE REQUIRED |
| | LICENSE INFORMATION FOR MARK ROBINSON |
| | DESIGN , LLC. |
| | PLEASE SEE FS 481.219, FS 471.023 FOR |
| | MISSING CERTIFICATE OF AUTHORIZATION #. |
| | WHAT TYOE OF BUSINESS IS THIS? IF |
| | ARCHITECT WORKS FOR THIS DESIGN FIRM, |
| | PLEASE INCLUDECA #. |
| | 61G1-16.004 |
| | |
| | 5) NOTE: PLEASE SEE MAX OCP FOR AHU IS |
| | TYPICALL 150% , HOWEVER PANEL SCHEDULE |
| | SHOWS 60A OCP FOR 5KW HEAT IN AHU? |
| | PLEASE SEE 424.3B FOR MIN @125%. |
| | PLEASE ALSO SEE #6, SHOWN WHICH IS OK, |
| | HOWEVER IF SHOWN ON PLANS, #6 WILL BE |
| | REQUIRED. PLEASE ALSO KNOW, IF THE 5KW |
| | UNTI CONTAINS THE TYPICAL 30A OCP, #6 |
| | WILL NOT INSERT INTO A 30A BRKR. |
| | PLEASE ADJUST. |
| | 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE 250.50, AS THE NEW |
| | "FOOTER STEEL" SHALL BE PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. |
| | PLEASE ALSO CLARIFY THE "STRUCTURAL |
| | STEEL" AS NOTED.?? |
| | |
| | 7) NOTE: PLEASE SEE 110.26 FOR MIN |
| | CLEARENCES FOR THE CU/ AHU DISC'S. |
| | |
| | 8) NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | FOR CU'S. (BOTH) |
| | 210.63, 210.8A3 |
| | |
| | 9) NOTE: PLEASE VERIFY CIRCUITING OF LT |
| | OUTSIDE BATH #3, AS LTS IN THE SAME SW |
| | BOX ARE ON 19, HOWEVER LT FOR THE LT |
| | ADJACENT IS ON THE MASTER BEDRM/EXT |
| | RECEPT CIRCUIT. THIS IS OK, HOWEVER IF |
| | SHOWN, THIS IS REQUIRED. THIS IS ONLY |
| | NOTED FOR INFORMATIONAL PURPOSE AND THIS |
| | DOES NOT REQUIRE CHANGE. |
| | THIS CAN BE REVISED AT A LATER DATE, AS |
| | OTHER REVISIONS WILL MOST LIKELY TAKE |
| | PLACE. |
| | |
| | 10) NOTE: PLEASE SEE SOME ELECTRICAL |
| | DEVICES ON PLANS ARE MISSING CIRCUITING. |
| | 408.4. |
| | |
| | 11) NOTE: PLEASE LIST ALL THE REQUIRED |
| | ARC FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PLEASE SEE ARC FAULT IS ONLY |
| | SHWON FOR THE SD/LTS CIRCUIT AND ARC |
| | FUALT IS ONLY NOTED ON PLANS FOR RECEPTS |
| | NOT ALL AS REQUIRED PER 2002 NEC 210.12B |
| | PLEASE LIST ON SCHEDULE. 408.4. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |