| 2006-07-26 00:00:00 | |
| | |
| | DENIED |
| | |
| | THE FOLLOWING NOTES WERE NOT ADDRESSED |
| | ON THE FIRST REVIEW |
| | |
| | 5) PROVIDE SIGNED AND DATED ENERGY |
| | CALC'S BE SURE THEY ARE SIGNED AND DATED |
| | BY PREPARER AND OWNER/AGENT |
| | ***(OWNER/AGENT HAS NOT SIGNED)*** |
| | |
| | 15) PROVIDE WOOD CONNECTORS THAT TIE |
| | TRUSSES TO GIRDERS AT VARIOUS LOCATIONS |
| | AND STRAPS TO BE USED AT VALLEY SETS |
| | ***(TRUSS DRAWINGS TO BE REVIEWED AND |
| | APPROVED BY DESIGNER OF RECORD PLEASE |
| | NOTE THAT THE DRAWINGS FOR TRUSS TO |
| | TRUSS AND VALLEY ATTACHMENT IS BY |
| | OTHERS)PLEASE PROVIDE ATTACHMENT THAT |
| | MEETS REQUIRED UPLIFTS*** |
| | |
| | 1) ONLY ONE COPY OF SOIL REPORT WAS |
| | SUBMITTED |
| | |
| | 2) SEE ZONING COMMENTS SITE PLAN TO |
| | MATCH SETBACKS ON SURVEY |
| | |
| | 3) PRODUCT APPROVAL FOR HORIZNTAL |
| | SLIDERS HAVE A MAXIMUM WIDTH OF 74" |
| | WINDOW TYPE #5 ON SCHEDULE IS 106 1/4" |
| | WIDE. |
| | |
| | 4) PLEASE STATE TYPE OF GLASS ON THE |
| | HORIZONTAL SLIDER AS THE MIN GLASS TYPE |
| | DOES NO MEET THE REQUIRED PRESSURE ON |
| | THE SCHEDULE (SEE PAGE 1 OF 6 IN PRODUCT |
| | APPROVAL DRAWING) |
| | |
| | 5) WINDOW PRESSURES FROM PRODUCT |
| | APPROVALS DO NOT MATCH SCHEDULE ON 5/12 |
| | PLEASE MATCH OR DELETE THIS INFORMATION |
| | |
| | 6) WINDOW SIZE SKETCH FOR SH25 (WINDOW |
| | #4 ON SCEDULE) SHOWS A SH24 PLEASE |
| | CLARIFY |
| | |
| | 7) NO PRODUCT APPROVALS WERE SUBMITTED |
| | FOR REGULAR PANEL DOORS (#8 & #9 ON |
| | SCHEDULE) |
| | |