| Plan Review Notes For Permit 06040623 |
| Permit Number |
06040623 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-08 00:00:00 | *** DENIED *** | | | 1) ARCHITECT PRINTED NAME, LICENSE | | | NUMBER, ADDRESS, AND PHONE NUMBER, PER | | | TITLE BLOCK,FAC 61G1-16.004. | | | | | | 2) PLEASE SUBMIT ENERGY CALCULATIONS | | | FORM 600A-04 (2004) PER FBC 13-600.3.A . | | | | | | 3) PLEASE SUBMIT A MANUAL J CALCULATION, | | | PER 2004 FBC 13-607.1.ABC.1 . | | | | | | 4) DRYER VENT EXHAUST MUST TERMINATE A | | | MIN. OF FOUR FEET FROM THE A/C CONDENSER | | | UNIT, PER 2004 FBC/M 401.5.2 . | | | | | | 5) ELECTRICAL PLANS ARE CALLING FOR A 10 | | | KW HEATER, AND MECHANICAL PLANS ARE | | | CALLING FOR A 5 KW HEATER, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|