| 2006-05-05 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE 1/0 SERVICE CONDUCTORS SHOWN ON | | | THE RISER DIAGRAM ARE NOT LARGE ENOUGH | | | FOR A 200 AMP SERVICE. SEE 310.15(B)(6). | | | | | | 2} PLEASE LOCATE THE 200 AMP MAIN | | | DISCONNECT ON THE PLAN . | | | | | | 3} PLEASE SEE THAT SMOKE DETECTORS MUST | | | BE ON AN ARC FAULT CIRCUIT PER 210.12. | | | | | | 4} A RECEPTACLE MUST BE ADDED TO THE | | | REAR OF THE HOUSE PER 21.52(E). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|