2006-05-05 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 1/0 SERVICE CONDUCTORS SHOWN ON
 THE RISER DIAGRAM ARE NOT LARGE ENOUGH
 FOR A 200 AMP SERVICE. SEE 310.15(B)(6).
  
 2} PLEASE LOCATE THE 200 AMP MAIN
 DISCONNECT ON THE PLAN .
  
 3} PLEASE SEE THAT SMOKE DETECTORS MUST
 BE ON AN ARC FAULT CIRCUIT PER 210.12.
  
 4} A RECEPTACLE MUST BE ADDED TO THE
 REAR OF THE HOUSE PER 21.52(E).
  