Plan Review Notes
Plan Review Notes For Permit 06040623
Permit Number 06040623
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-23 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. PERMIT FEES
 WILL BE INCREASED ACCORDINLY
  
 3) A DESIGN PROFESSIONAL THAT IS
 REGISTERED TO PRACTICE UNDER CHAPTER 481
 OR 471 OF THE FLORIDA STATUTES SHALL
 AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004. THE DATE IS MISSING
 ALSO THERE IS A MISTAKE ON THE LICENCE#
  
 4) PROVIDE UNDER ROOF SQ FT OF ADDITION,
 CARPORT AND FRONT PORCH. THESE ARE
 REQUIRED FOR COUNTY IMPACT FEES AND
 STATE RADON FEE
  
 5) PROVIDE SIGNED AND DATED ENERGY
 CALC'S BE SURE THEY ARE SIGNED AND DATED
 BY PREPARER AND OWNER/AGENT
  
 6) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 7) PROVIDE COPY OF SURVEY THAT IS LESS
 THAN 1 YR OLD
  
 8) PROVIDE PRODUCT APPROVAL FOR WOOD
 CONNECTORS/HURRICANE STRAPS (SEE
 ATTACHED SHEETS, THIS METHOD WHERE THE
 FL# AND THE CONNECTORS USED ARE MARKED
 IS ADEQUATE)
  
 9) PRODUCT APPROVALS DO NOT MATCH
 DRAWINGS, NOSH WINDOW APPROVALS BUT ALL
 OPENING WINDOWS ON DRAWING SPECIFY SH.
 APPROVALS FOR CASEMENT AND HORIZONTAL
 SLIDERS BUT NONE SPECIFIED ON DRAWINGS.
 FIXED WINDOW APPROVALS ARE NON-IMPACT AS
 SUCH WILL REQUIRE OPENING PROTECTIVES,
 SUBMIT PRODUCT APPROVALS. ALL PRODUCT
 APPROVAL DRAWINGS ARE MISSING DATA AS
 PRINTING SEEMED TO CUT OF TOP OF DRWGS
  
 10) IF THESE PRODUCTS ARE TO BE USED
 UPDATE WINDOW SCHEDULE AND DRAWINGS TO
 REFLECT CHANGES
  
 11) CORRECT BLDG DESIGN DATA ON PAGE 1
  
 12) FOUNDATION SHALL BE A MINIMUM OF 12"
 BELOW GRADE PER R403.1.4 FBC (SEE DETAIL
 1/8 ON PG.8
  
 13) PROVIDE DETAILS ON PORCH BEAM AND
 RAFTER ATTACHMENT TO BEAM AND TIE IN TO
 EXISTING ROOF.
  
 14) PROVIDE DETAILS ON CARPORT BEAMS
  
 15) PROVIDE WOOD CONNECTORS THAT TIE
 TRUSSES TO GIRDERS AT VARIOUS LOCATIONS
 AND STRAPS TO BE USED AT VALLEY SETS
  
 16) PERMIT APPLICATION STATES
 REPLACEMENT OF WINDOWS AND ROOF IN
 EXISTING STRUCTURE, PLEASE CLARIFY, IF
 SHINGLE ARE TO BE RELACED ON ENTIRE ROOF
 SPECIFY ON DRAWING. LIKEWISE FOR WINDOWS
 AS ONLY A FEW ARE TO BE REMOVED AS PER
 DEMO PLAN
  
 17) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  