| Plan Review Notes For Permit 06040598 |
| Permit Number |
06040598 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-27 00:00:00 | DENIED; | | | 1.PAGE A-7; (4) INTERIOR ELEVATION. SHOW | | | MEASUREMENTS OFF WALL FOR HANDICAP | | | TOILET, 18" AND 5" TO THE EDGE OF | | | LAVATORY OFF WALL. SHOW GRAB BARSON | | | DETAIL DRAWING AND FLOOR PLAN. | | | 2.PAGE PO.1 WATER HEATER DETAIL; A MEANS | | | OF THERMAL EXPANSION CONTROL IS REQUIRED | | | PER FBC-2004 PLUMBING SEC.607.3. SHOW ON | | | PLAN. | | | 3.GREASE TRAP NOT PERMITED IN FOOD PREP | | | AREA. GREASE TRAP TO BE SIZED BY THE | | | UTILITY DEPARTMENT. WASTE ORDENANCE | | | #3434. PLEASE CONTACT; | | | LYNN MASSON | | | (561) 822-2271 | | | (561) 822-2279 | | | E-MAIL [email protected]. | | | 4. MOP SINK AND FLOOR DRAIN IN FOOD PREP | | | AREA TO GO TO GREASY WASTE. | | | 5.WATER RISER PAGE P5.1 WATER HAMMER | | | ARRESTORS TO BE INSTALLED AS CLOSE TO | | | THE SOURE OF HAMMER AS POSSIBLE. PLEASE | | | SHOW ON DRAWING TO COMPLY WITH YOUR NOTE | | | #13 ON PAGE P0.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|