| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SEE THAT IN THE ELECTRICAL |
| | SPECIFICATIONS(NOTES) THE 2001 FBC IS |
| | INCORRECTLYREFERENCED, PLEASE |
| | REFERENCE THE 2004 FBC. THE "LATEST |
| | EDITION OF THE NEC" IS MENTIONED IN PART |
| | 3 C. THE 2002 EDITION IS THE ADOPTED |
| | CODE FOR THE STATE OF FLORIDA, THE |
| | CURRENT NEC IS 2005. ALSO SEE |
| | "DESIGN CODES" ON SHEET T1 ARE ALL |
| | CORRECT EXCEPT THE 2003 NEC. |
| | |
| | PLEASE REFERENCE THE ADOPTED EDITIONS OF |
| | ALL CODE USED IN NOTES OR REFERENCES. |
| | |
| | 2} CIRCUIT "B1-34" IS MISLABLED AS A |
| | SPARE, SHOULD BE ROOF RECEPTACLE. |
| | |
| | 3} THE #1/0 GEC SHOULD BE INCREASED FOR |
| | A 600 AMP SERVICE. SEE 250.66. |
| | |
| | 4} FORM 400A WAS SUBMITTED FOR ENERGY |
| | CODE REQUIREMENTS. PLEASE SHOW CAUSE WHY |
| | THE PRESCRIPTIVE REQUIREMENTS PER |
| | 13-101.1.3 SHOULD NOT BE MET AND FORM |
| | 400C SUBMITTED, AS THIS IS A RENOVATION. |
| | |
| | 5} SUBMIT THE AIC RATING OF THE NEW |
| | SERVICE DISCONNECT PER 110.9. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |