| Plan Review Notes For Permit 06040588 |
| Permit Number |
06040588 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-04 00:00:00 | | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE WHETHER NG OR LP. | | | | | | 2} SUBMIT A RISER DIAGRAM INDICATIG THE | | | ELECTRICAL LOCATION OF BOTH THE | | | GENERATOR AND SERVICE EQUIPMENT. SEE | | | 230.72 FOR GROUPING OF DISCONNECTS, | | | 225.31-39 FOR LOCATION AND RATINGS, | | | 250.32 AND 250.66 FOR GROUNDING. | | | | | | 3} SUBMIT A PANEL SCHEDULE AND A LOAD | | | CALCULATION FOR THE LOAD SERVED BY THE | | | GENERATOR. SEE 702.5. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|