 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE WHETHER NG OR LP.
  
 2} SUBMIT A RISER DIAGRAM INDICATIG THE
 ELECTRICAL LOCATION OF BOTH THE
 GENERATOR AND SERVICE EQUIPMENT. SEE
 230.72 FOR GROUPING OF DISCONNECTS,
 225.31-39 FOR LOCATION AND RATINGS,
 250.32 AND 250.66 FOR GROUNDING.
  
 3} SUBMIT A PANEL SCHEDULE AND A LOAD
 CALCULATION FOR THE LOAD SERVED BY THE
 GENERATOR. SEE 702.5.
  