2006-05-10 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- WIND LOAD CALCULATIONS SUBMITTED ARE
 FOR GABLE ROOFS. THIS BUILDING HAS A
 FLAT ROOF. ENGINEER TO REVISE
 CALCULATIONS AS REQUIRED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 AND CHAPTER
 16 FBC 2004.
  
 2- ENGINEER TO REVISE RAS 117
 CALCULATIONS TO REFLECT THE REVISED
 DESIGN PRESSURES. SEE ITEM #1.
  
 3- A) EVERY DOCUMENT PREPARED BY THE
 PROFESSIONAL ENGINEER NEED TO HAVE
 ORIGINAL SEAL, SIGNATURE AND DATE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND FLORIDA ADMINISTRATIVE CODE. PROVIDE
 2 COPIES OF EVERY DOCUMENT.
 B) ENGINEER TO PROVIDE HIS NAME AND
 LICENSE # ON EVERY SIGNED AND SEALED
 SHEET AS REQUIRED BY 61G15-23.002 OF
 DEPARTMENT OF COMMUNITY AFFAIRS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712