2006-04-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- A) CLEARLY IDENTIFY WHICH APPROVED
 FLAT ROOF SYSTEM IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH
 GENERAL LIMITATION #7 OR #9. SEE CITY
 ATTACHED COPY OF CITY POLICY FOR
 RE-ROOFING PERMIT REQUIREMENTS.
 B) CLEARLY SPECIFY TYPE OF MEMBRANE
 AND FASTENERS TO BE USED ON SELECTED
 APPROVED ASSEMBLY.
  
 2- WIND UPLIFT PRESSURE CALCULATIONS TO
 BE SIGNED AND SEALED BY ENGINEER WHO DID
 THE CALCULATIONS AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
  
 3- ROOF DIMENSIONS SHOWN ON WIND UPLIFT
 CALCULATIONS DON'T MATCH ACTUAL BUILDING
 DIMENSIONS AND BUILDING SHAPE. REVISE AS
 REQUIRED.
  
 4- PROVIDE COMPLETE PROJECT ADDRESS AND
 CONTRACTOR INFORMATION ON TOP OF FORM.
  
 5- GENERAL LIMITATION #7 ON LAST PAGE OF
 DADE COUNTY NOA REPORT REQUIRES
 CALCULATIONS TO BE DONE USING RAS 117.
 PROVIDE SUCH CALCULATIONS. SEE GENERAL
 LIMITATION #7.
  
 6- A) WIND UPLIFT PRESSURES CALCULATIONS
 SHEET IS MISSING WHICH DADE COUNTY NOA
 ARE CALCULATIONS DONE FOR. SEE BOTTOM OF
 SHEET AND PROVIDE INFORMATION AS REQ'D.
 B) WIND UPLIFT CALCULATIONS ARE
 REFERING TO FLORIDA FL1599-R3 SYSTEM
 R-2. UNABLE TO FIND THIS INFORMATION IN
 THE FLORIDA WEBSITE. SEE BOTTOM OF SHEET
 AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712