| 2006-04-17 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- A) CLEARLY IDENTIFY WHICH APPROVED |
| | FLAT ROOF SYSTEM IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH |
| | GENERAL LIMITATION #7 OR #9. SEE CITY |
| | ATTACHED COPY OF CITY POLICY FOR |
| | RE-ROOFING PERMIT REQUIREMENTS. |
| | B) CLEARLY SPECIFY TYPE OF MEMBRANE |
| | AND FASTENERS TO BE USED ON SELECTED |
| | APPROVED ASSEMBLY. |
| | |
| | 2- WIND UPLIFT PRESSURE CALCULATIONS TO |
| | BE SIGNED AND SEALED BY ENGINEER WHO DID |
| | THE CALCULATIONS AS REQUIRED BY CHAPTER |
| | 471 FLORIDA STATUTES AND FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 3- ROOF DIMENSIONS SHOWN ON WIND UPLIFT |
| | CALCULATIONS DON'T MATCH ACTUAL BUILDING |
| | DIMENSIONS AND BUILDING SHAPE. REVISE AS |
| | REQUIRED. |
| | |
| | 4- PROVIDE COMPLETE PROJECT ADDRESS AND |
| | CONTRACTOR INFORMATION ON TOP OF FORM. |
| | |
| | 5- GENERAL LIMITATION #7 ON LAST PAGE OF |
| | DADE COUNTY NOA REPORT REQUIRES |
| | CALCULATIONS TO BE DONE USING RAS 117. |
| | PROVIDE SUCH CALCULATIONS. SEE GENERAL |
| | LIMITATION #7. |
| | |
| | 6- A) WIND UPLIFT PRESSURES CALCULATIONS |
| | SHEET IS MISSING WHICH DADE COUNTY NOA |
| | ARE CALCULATIONS DONE FOR. SEE BOTTOM OF |
| | SHEET AND PROVIDE INFORMATION AS REQ'D. |
| | B) WIND UPLIFT CALCULATIONS ARE |
| | REFERING TO FLORIDA FL1599-R3 SYSTEM |
| | R-2. UNABLE TO FIND THIS INFORMATION IN |
| | THE FLORIDA WEBSITE. SEE BOTTOM OF SHEET |
| | AND REVISE AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |