| Plan Review Notes For Permit 06040510 |
| Permit Number |
06040510 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-12 00:00:00 | | | | PROVISO | | | | | | | | | VERTICAL CLEARANCE MUST COMPLY WITH | | | 230.24(A): | | | | | | 230.24(A) | | | ABOVE ROOFS. CONDUCTORS SHALL HAVE A | | | VERTICAL CLEARANCE OF NOT LESS THAN 2.5 | | | M (8 FT) ABOVE THE ROOF SURFACE. THE | | | VERTICAL CLEARANCE ABOVE THE ROOF LEVEL | | | SHALL BE MAINTAINED FOR A DISTANCE OF | | | NOT LESS THAN 900 MM (3 FT) IN ALL | | | DIRECTIONS FROM THE EDGE OF THE ROOF. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|