Plan Review Notes
Plan Review Notes For Permit 06040510
Permit Number 06040510
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-12 00:00:00 
 PROVISO
  
  
 VERTICAL CLEARANCE MUST COMPLY WITH
 230.24(A):
  
 230.24(A)
 ABOVE ROOFS. CONDUCTORS SHALL HAVE A
 VERTICAL CLEARANCE OF NOT LESS THAN 2.5
 M (8 FT) ABOVE THE ROOF SURFACE. THE
 VERTICAL CLEARANCE ABOVE THE ROOF LEVEL
 SHALL BE MAINTAINED FOR A DISTANCE OF
 NOT LESS THAN 900 MM (3 FT) IN ALL
 DIRECTIONS FROM THE EDGE OF THE ROOF.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW