| Plan Review Notes For Permit 06040510 |
| Permit Number |
06040510 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-17 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} 230.24(B) VERTICAL CLEARANCE FROM | | | GROUND. SERVICE-DROP CONDUCTORS, WHERE | | | NOT IN EXCESS OF 600 VOLTS, NOMINAL, | | | SHALL HAVE THE FOLLOWING MINIMUM | | | CLEARANCE FROM FINAL GRADE: | | | (1) 3.0 M (10 FT) ? AT THE ELECTRIC | | | SERVICE ENTRANCE TO BUILDINGS, ALSO AT | | | THE LOWEST POINT OF THE DRIP LOOP OF THE | | | BUILDING ELECTRIC ENTRANCE, AND ABOVE | | | AREAS OR SIDEWALKS ACCESSIBLE ONLY TO | | | PEDESTRIANS, MEASURED FROM FINAL GRADE | | | OR OTHER ACCESSIBLE SURFACE ONLY FOR | | | SERVICE-DROP CABLES SUPPORTED ON AND | | | CABLED TOGETHER WITH A GROUNDED BARE | | | MESSENGER WHERE THE VOLTAGE DOES NOT | | | EXCEED 150 VOLTS TO GROUND | | | | | | 2} PERSON TAKING RESPONSIBILITY FOR THE | | | PLAN PLEASE PRINT AND SIGN NAME. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|