Plan Review Notes
Plan Review Notes For Permit 06040510
Permit Number 06040510
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-17 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 230.24(B) VERTICAL CLEARANCE FROM
 GROUND. SERVICE-DROP CONDUCTORS, WHERE
 NOT IN EXCESS OF 600 VOLTS, NOMINAL,
 SHALL HAVE THE FOLLOWING MINIMUM
 CLEARANCE FROM FINAL GRADE:
 (1) 3.0 M (10 FT) ? AT THE ELECTRIC
 SERVICE ENTRANCE TO BUILDINGS, ALSO AT
 THE LOWEST POINT OF THE DRIP LOOP OF THE
 BUILDING ELECTRIC ENTRANCE, AND ABOVE
 AREAS OR SIDEWALKS ACCESSIBLE ONLY TO
 PEDESTRIANS, MEASURED FROM FINAL GRADE
 OR OTHER ACCESSIBLE SURFACE ONLY FOR
 SERVICE-DROP CABLES SUPPORTED ON AND
 CABLED TOGETHER WITH A GROUNDED BARE
 MESSENGER WHERE THE VOLTAGE DOES NOT
 EXCEED 150 VOLTS TO GROUND
  
 2} PERSON TAKING RESPONSIBILITY FOR THE
 PLAN PLEASE PRINT AND SIGN NAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW