| Plan Review Notes For Permit 06040505 |
| Permit Number |
06040505 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-17 00:00:00 | *** DENIED *** | | | 1) PLEASE SUBMIT MANUAL J CALCULATIONS, | | | PER 2004 FBC/R M1401.3 . | | | | | | 2) PLEASE SHOW COPPER LINE SIZES ON | | | MECH. PLAN. | | | | | | 3) PLEASE SHOW JOB ADDRESS ON MECH. | | | PLANS. | | | | | | 4) A 12" RETURN AIR DUCT IS TO SMALL FOR | | | A 3.5 TON A/C SYSTEM, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|