| Plan Review Notes For Permit 06040474 |
| Permit Number |
06040474 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-06-07 00:00:00 | ************* PROVISO ************** | | | | | | ** PLEASE KNOW, NO INSPECTIONS ARE TO BE | | | DONE UNTIL THE BELOW NOTES ARE ADDESSED, | | | SUBMITTED AND PASSED FOR REVIEW. REVISED | | | PLANS WILL PAY REVISION FEES AND MUST BE | | | ON JOBSITE BEFORE ANY SUCH INSPECTIONS. | | | | | | 1) NOTE: PLEASE SEE PLANS REFLECT AND | | | NOTE THE 2005 NFPA-101 WHEN WE ARE UNDER | | | THE 2003 EDITION. | | | | | | 2) NOTE: PLEASE SEE NOTE #2 FROM | | | PREVIOUS REVIEW. | | | PLEASE VERIFY LOAD ON EXISTING SERVICE | | | WITH NEW LOADS ADDED. | | | PLEASE SEE THE EXISTING LOAD SHOULD BE | | | SHOWN WITH NEW LOADS BEING ADDED. | | | | | | 220,220.35 ETC | | | THESE MUST BE DONE AND ANY INSTALLATION | | | OF ANY SERVICE EQUIPMENT BEFORE | | | VERIFICATION OF SERVICE AND LOADS IS | | | DONE AT THE CONTRACTORS OWN RISK AND CAN | | | BE SUBJECT TO REMOVAL AND REPLACEMENT OF | | | NEWER OR LARGER SERVICE EQUIPMENT | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|