| Plan Review Notes For Permit 06040455 |
| Permit Number |
06040455 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- A) FLORIDA PRODUCT APPROVAL SUBMITTED | | | DOESN'T SPECIFY DESIGN PRESSURES FOR | | | WHICH PRODUCT WAS DESIGNED. | | | B) SUBMIT ENGINEERING CALCULATIONS | | | FOR WIND LOAD AND PROVIDE COMPLETE | | | INSTALLATION SPECIFICATIONS TO EXISTING | | | STRUCTURE TO MEET THE CALCULATED LOADS | | | AS REQUIRED BY SEC. 1609 FBC 2004 AND | | | SECTION 106.1.2CITY AMENDMENTS TO FBC | | | 2004. ENGINEERING PACKAGE TO BE SIGNED | | | AND SEALED AS REQUIRED BY CHAPTER 471 | | | FLORIDA STATUTES AND 61G15-23.002 OF | | | FLORIDA ADMINISTRATIVE CODE. | | | C) SPECIFICATIONS TO INCLUDE LIVE AND | | | DEAD LOADS AS REQUIRED BY SECTIONS 1606 | | | AND 1607 FBC 2004. | | | | | | 2- PROFESSIONAL PROVIDING ABOVE | | | CALCULATIONS TO REVIEW AND APPROVE IN | | | WRITTING THIS STRUCTURAL METAL ROOF | | | SYSTEM PRODUCT APPROVAL AS REQUIRED BY | | | SECTION 106.3.3 OF CITY AMENDMENTS TO | | | FBC 2004. | | | | | | 3- PROVIDE RECORDED NOTICE OF | | | COMMENCEMENT AS REQUIRED BY SECTION | | | 713.13 FLORIDA STATUTES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|