| Plan Review Notes For Permit 06040438 |
| Permit Number |
06040438 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-25 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A LOAD CALCULATION FOR | | | THE LOAD BEING SERVED BY THE GENERATOR. | | | LOAD CANNOT EXCEED GENERATOR OUTPUT, SEE | | | 702.5, 2002 NEC. | | | | | | 2} SHOW ALL SERVICE EQUIPMENT AND | | | GENERATOR ATS AND GENERATOR LOCATIONS ON | | | THE SITE PLAN. I SEE THE ATS AND | | | GENERATOR, BUT MAINS MUST BE GROUPED, | | | 270.72, DISCONNECTS MUST BE SERVICE | | | RATED, 225.31-39. IT IS UNCLEAR HOW | | | COMPLIANCE IS MAINTAINED WITHOUT SEEING | | | ALL OTHER PANELS AND DISCONNECTS. | | | | | | 3} SUBMIT A PANEL SCHEDULE FOR THE ATS | | | PANEL. 106.3.5.4 FBC. | | | | | | THIS PERMIT CANNOT BE ISSUED UNTILL A | | | RESIDENTIAL GENERATOR PERMIT IS ISSUED. | | | THERE WAS ELECTRICAL, GAS, AND | | | GENERATOR PERMITS APPLIED FOR LAST YEAR. | | | SPEAK TO THE OWNER REGARDING THIS ISSUE. | | | THE APPLICATION REQUIREMENTS FOR A | | | GENERATOR PERMIT ARE ATTACHED FOR YOUR | | | REFERENCE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|