| 2006-09-05 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW PRIOR TO ROUGH INSPECTION. ALLOW |
| | AT LEAST ONE WEEK IN REVIEW. SHEET E-01 |
| | IS THE ONLY REVISION REQUIRED FOR THIS |
| | REVIEW. OTHER SHEETS NEED ONLY BE |
| | REVISED FOR FIELD CHANGES. |
| | |
| | THE GROUNDING ELECTRODE CONDUCTOR SHOULD |
| | BE CONNECTED TO THE GROUNDED (NEUTRAL) |
| | CONDUCTOR IN THE GUTTER, AHEAD OF THE |
| | INDIVIDUAL METERS, COMMON TO ALL FEEDS, |
| | BOTH SERVICES. SEE ILLISTRATION 250.10, |
| | 2002 NEC HANDBOOK. |
| | |
| | THE GROUNDING ELECTRODE CONDUCTOR MUST |
| | BE 3/0 CU. ON BUILDING "A" TO COMPLY |
| | WITH 250.66. |
| | |
| | THERE SHOULD NOT BE A GROUND WIRE IN THE |
| | RISER. 250.6, BOTH SERVICES. |
| | |
| | THE NOTE "TYPICAL BEFORE AND AFTER |
| | METER", AND THE GROUND FROM THE GUTTER |
| | TO THE METER SHOWN IN BUILDING "B" |
| | SERVICE, SHOULD BE REMOVED. 250.6, |
| | OBJECTIONABLE CURRENTS, PARALLELING |
| | PATHS. |
| | |
| | SEE BUILDING PLAN REVIEW NOTES AND |
| | REVISE ELECTRICAL PLANS AS NEEDED. |
| | INCORPORATE ELECTRICAL PLANS INTO THE |
| | SUBMITTED SET, REMOVE OLD SHEETS, |
| | SUBMIRT ONE SET OF OLD SHEETS TO AID |
| | REVIEW. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |