2006-09-05 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION. ALLOW
 AT LEAST ONE WEEK IN REVIEW. SHEET E-01
 IS THE ONLY REVISION REQUIRED FOR THIS
 REVIEW. OTHER SHEETS NEED ONLY BE
 REVISED FOR FIELD CHANGES.
  
 THE GROUNDING ELECTRODE CONDUCTOR SHOULD
 BE CONNECTED TO THE GROUNDED (NEUTRAL)
 CONDUCTOR IN THE GUTTER, AHEAD OF THE
 INDIVIDUAL METERS, COMMON TO ALL FEEDS,
 BOTH SERVICES. SEE ILLISTRATION 250.10,
 2002 NEC HANDBOOK.
  
 THE GROUNDING ELECTRODE CONDUCTOR MUST
 BE 3/0 CU. ON BUILDING "A" TO COMPLY
 WITH 250.66.
  
 THERE SHOULD NOT BE A GROUND WIRE IN THE
 RISER. 250.6, BOTH SERVICES.
  
 THE NOTE "TYPICAL BEFORE AND AFTER
 METER", AND THE GROUND FROM THE GUTTER
 TO THE METER SHOWN IN BUILDING "B"
 SERVICE, SHOULD BE REMOVED. 250.6,
 OBJECTIONABLE CURRENTS, PARALLELING
 PATHS.
  
 SEE BUILDING PLAN REVIEW NOTES AND
 REVISE ELECTRICAL PLANS AS NEEDED.
 INCORPORATE ELECTRICAL PLANS INTO THE
 SUBMITTED SET, REMOVE OLD SHEETS,
 SUBMIRT ONE SET OF OLD SHEETS TO AID
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW