Plan Review Notes
Plan Review Notes For Permit 06040434
Permit Number 06040434
Review Stop P
Sequence Number 2
Notes
Date Text
2006-09-09 00:00:00DENIED;
 1.BATHROOMS TO BE HANDICAP ACCESSIBLE.
 FBC-2004 EXISTING BUILDING CODE SECTION
 606.1. SHOW SIZE OF BATHROOM, CLEAR
 FLOOR SPACE, AND TURNING RADIUS IN ALL
 BATHROOMS. BATHROOM DOORS CAN NOT SWING
 INTO THE CLEAR FLOOR SPACE OF THE
 LAVATORY.
 2.EXISTING BUILDING CODE SECTION 810.1,
 IF THERE IS AN OCCUPANCY CHANGE THE NEW
 OCCUPANCY IS SUBJECT TO DIFFERENT
 PLUMBING FIXTURE REQUIREMENTS. SEE
 FBC-2004 PLUMBING TABLE 403.1. DRINKING
 FOUNTAINS WOULD BE REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695