| 2006-09-08 00:00:00 | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. THE NOC THAT WAS |
| | SUBMITTED DOES NOT HAVE THE RECORDING |
| | STAMP ON IT. |
| | |
| | 2) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. SUBMIT PRODUCT APPROVALS FOR |
| | THE NEW EXTERIOR WINDOWS AND DOORS. IF |
| | GLAZING IS NOT IMPACT RESISTANT, STORM |
| | PANEL PRODUCT APPROVALS ARE REQUIRED |
| | ALONG WITH AN INSTALLATION SCHEDULE AND |
| | KEY PLAN. |
| | |
| | 3) THE DESCRIPTION OF WORK ON THE PERMIT |
| | APPLICATION DOES NOT REFLECT THE SCOPE |
| | OF WORK SPECIFIED ON THE PLANS. PLEASE |
| | REVISE AND INCREASE THE VALUE OF THE |
| | WORK LISTED ON THE PERMIT APPLICATION |
| | ACCORDINGLY. |
| | |
| | 4) SPECIFY THE LEVEL OF ALTERATION FOR |
| | THE PROJECT THE ON THE PLANS, AS |
| | SPECIFIED IN THE 2004 FBC EXISTING |
| | BUILDING CODE. |
| | |
| | 5) THE BUILDINGS OCCUPANCIES ARE LISTED |
| | AS BUSINESS ON SHEET CS. HOWEVER, |
| | OCCUPANT LOADS ARE GIVEN FOR BUSINESS |
| | AND WAREHOUSE(STORAGE). IT APPEARS TO BE |
| | MIXED OCCUPANCIES (STORAGE, BUSINESS AND |
| | POSSIBILY FACTORY OCCUPANCIES). SPECIFY |
| | THE OCCUPANCY AND OCCUPANT LOAD OF EACH |
| | TENANT SPACE. SPECIFY THE TYPE OF |
| | STORAGE(FBC 311).SEE FBC 302 & 302.3. |
| | |
| | 6) SPECIFY THE REQUIRED FIRE-RESISTANCE |
| | RATINGS OF THE TENANT SEPARATION WALLS. |
| | SEE FBC 302.3.2 AND TABLE 302.3.2. |
| | |
| | 7) SPECIFY THE FIRE RATING OF THE TENANT |
| | SEPARATION WALL BETWEEN SUITES 3 AND 4 |
| | IN BUILDING #2. |
| | |
| | 8) SPECIFY THE FIRE RATING OF THE TENANT |
| | SEPARATION WALL (NEW AND EXISTING) |
| | DIVIDING THE AREA OF BUILDING #1 INTO |
| | TWO SEPARATE SPACES. |
| | |
| | 9) A FIRE BARRIER IS REQUIRED TO |
| | SEPARATE THE ACCESSORY USE AREA OF THE |
| | BUSINESS AREA FROM THE LARGE |
| | STORAGE/WAREHOUSE AREA IN BUILDING #1. |
| | THE BUSINESS AREA IS MORE THAN 10 PER |
| | CENT OF THE AREA IN WHICH IT IS LOCATED. |
| | SEE FBC 302.2. |
| | |
| | 10) PROVIDE DETAILS OF THE EXTERIOR WALL |
| | PATCHES. INDICATE MATERIAL, ATTACHMENTS, |
| | ETC. |
| | |
| | 11) THE TENANT BATHROOMS ARE REQUIRED TO |
| | BE ACCESSIBLE. FBC EXISTING BUILDING |
| | CODE SECTION 606.1. |
| | |
| | 12) INDICATE THE REQUIRED CLEAR FLOOR |
| | SPACE AT THE ACCESSIBLE FIXTURES ON THE |
| | PLANS. FBC 11-4.16.2, 11-4.19.3 AND |
| | 11-4.23.3. |
| | |
| | 13) DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | SEE FBC 11-4.23.2. |
| | |
| | 14) THE GRAB BAR AT THE REAR OF THE |
| | WATER CLOSET IN THE DETAIL ON A1 IS |
| | REQUIRED TO EXTEND A MINIMUM OF 12" PAST |
| | THE CENTER LINE OF THE FIXTURE ON BOTH |
| | SIDES. SEE FBC FIGURE 11-29(A). |
| | |
| | 15) FBC TABLE 602 REQUIRES EXTERIOR |
| | WALLS WITHIN 5' OF THE PROPERTY LINE TO |
| | HAVE A ONE HOUR FIRE RESISTANCE RATING. |
| | FBC TABLE 704.8 SPECIFIES THAT NO |
| | OPENINGS ARE ALLOWED IN EXTERIOR WALLS |
| | WITHIN 5' OF THE PROPERTY LINES IF THE |
| | WALLS ARE REQUIRED TO BE FIRE RATED. |
| | THEREFORE THE OPENINGS IN THESE WALLS |
| | ARE REQUIRED TO BE ENCLOSED WITH ONE |
| | HOUR RATED CONSTRUCTION. ONE HOUR FIRE |
| | RATED GLASS BLOCK MAY BE USED. |
| | |
| | NOTE: SEE NOTES AND MARKINGS ON PLAN. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |