Plan Review Notes
Plan Review Notes For Permit 06040434
Permit Number 06040434
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-14 00:00:00 
 THERE IS NOT SUFFICIENT CLARITY TO
 REVIEW THE PLANS SUBMITTED. PLEASE HAVE
 PLANS REDRAWN AND RESUBMIT SAME. 106.1.3
 FBC ADMINISTRATIVE SECTIION.
  
 THERE APPEARS TO BE ELECTRICAL SYMBOLS
 ON THE PLAN, PLEASE INDICATE IF ALL IS
 NEW WORK OR CLARIFY THE PORTION THAT IS.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN OF THE PLAN MUST PRINT NAME AND
 SIGN SAME. IF AN ARCHITECT OR ENGINEER,
 MUST BE IN COMPLIANCE WITH 481 AND 471
 FS. THE PLAN SUBMITTED HAS AN ENGINEERS
 TITLE BLOCK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026