| 2006-04-26 00:00:00 | | | | | | | PLEASE SEE THE FOLLOWING STATUTES AND | | | CODES AND RESUBMIT INDICATING COMPLIANCE | | | WITH SAME. | | | | | | | | | THE ENGINEERING FIRM WHOSE BUSINESS NAME | | | APPEARS IN THE TITLE BLOCK MUST INCLUDE | | | THEIR CERTIFICATE OF AUTHORIZATION | | | NUMBER PER 61G15-23. | | | | | | THE ELECTRICAL SCHEMATIC LACKS | | | SUFFICIENT CLARITY FOR REVIEW. SEE | | | 106.1.3 FBC. | | | | | | 600.6(A)(1) | | | THE DISCONNECTING MEANS SHALL BE WITHIN | | | SIGHT OF THE SIGN OR OUTLINE LIGHTING | | | SYSTEM THAT IT CONTROLS. WHERE THE | | | DISCONNECTING MEANS IS OUT OF THE LINE | | | OF SIGHT FROM ANY SECTION THAT MAY BE | | | ENERGIZED, THE DISCONNECTING MEANS SHALL | | | BE CAPABLE OF BEING LOCKED IN THE OPEN | | | POSITION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|