| Notes |
| Date |
Text |
| 2006-08-31 00:00:00 | ** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE OCP ON TH GENERATOR | | | SIZE IS AT 200A'S WHICH IS FEEDING #3'S. | | | PLEASE SEE 240.21, AS TAPPED CONDUCTORS | | | MUST TERMINATE IN OCP WHICH PROTECTS THE | | | CONDUCTORS. | | | PLEASE ALSO SEE AS THE EXISTING SUB | | | PANELS DOES NOT INDICATE ANY SIZES , NOR | | | DO THEY INDICATE A MCB WHICH WOULD ALSO | | | LIMIT THE LOAD. | | | PLEASE REVISE RISER. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE QUESTIONS, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|