| Notes |
| Date |
Text |
| 2006-05-15 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE NOTE #2 FROM | | | PREVIOUS REVIEW. PLEASE SEE MISSING | | | DISCONNECT FOR FEEDERS FROM GEN. | | | PLEASE SEE THIS DISCONNECT SHALL BE | | | GROUPED WITH EXISTING MAIN. | | | THIS DISICONNECT DOES NOT NEED TO | | | CONTAIN OCP, ONLY A DISCONNECTING MEANS | | | RATED FOR THE LOAD SERVED. | | | PLEASE SEE 225.31-225.39 | | | | | | 2) NOTE: PLEASE SEE EXISTING GE SYSTEM | | | IS NOW ONLY SHOWING A SINGLE GROUND ROD, | | | HOWEVER IT IS KNOW TO THIS OFFICE THAT | | | THE CWP SYSTEM IN THIS BUILDING IS | | | METAL. PLEASE SEE 250.50, 250.52 ETC. | | | | | | 3) NOTE: PLEASE HIGH LIGHT ATS BEING | | | INSTALLED, AS THE SPECS SUBMITTED | | | INDICATE MORE THAN ONE UNIT. | | | | | | | | | ** PLEASE SUBMIT TWO COMPLETE SETS WITH | | | ALL NEW SHEETS INSERTED INTO THE | | | COMPLETED SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|