| 2006-05-04 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | 1.)PROVIDE ANCHORING INFORMATION TO |
| | COMPLY WITH FBC1609.1.3; STRUCTURAL |
| | MEMBERS AND SYSTEMS, AND COMPONENTS AND |
| | CLADDING IN A BUILDING OR STRUCTURE |
| | SHALL BE ANCHORED TO RESIST WIND-INDUCED |
| | OVERTURNING, UPLIFT AND SLIDING AND TO |
| | PROVIDE CONTINUOUS LOAD PATHS FOR THESE |
| | FORCES TO THE FOUNDATION.WHERE A |
| | PORTION OF THE RESISTANCE TO THESE |
| | FORCES IS PROVIDED BY DEAD LOAD, THE |
| | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE |
| | DURING A DESIGN WIND EVENT SHALL BE |
| | USED. |
| | |
| | YOU HAVE PROVIDED INFORMATION IN REGARDS |
| | TO THE SLAB, AND PRODUCT INFORMATION WAS |
| | PROVIDED FOR TAPCONS, BUT THERE ARE |
| | SEVERAL DIFFERENT PRODUCTS ON THE SHEETS |
| | SUBMITTED WITH DIFFERENT VALUES. |
| | SPECIFY WHICH ANCHOR YOU ARE USING |
| | (CIRCLE) AND THE NUMBER OF ANCHORS TO BE |
| | USED. |
| | |
| | 2.)PROVIDE WIND DESIGN CRITERIA |
| | FBC1603.1.4. |
| | |
| | 3.)DOCUMENTS PREPARED BY AN ARCHITECT |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO |
| | BE SIGNED, SEALED, DATED ORIGINALS (SITE |
| | PLAN).NOTE THAT A SEALED SITE PLAN FOR |
| | THIS JOB IS NOT REQUIRED, BUT SINCE IT |
| | WAS PREPARED BY AN ARCHITECT IT IS |
| | REQUIRED TO BE SEALED. |