| 2006-04-19 00:00:00 | ********** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | FOR EXISTING LOADS INTENDED FOR USE. |
| | SINCE THE GEN WILL BE FEEDING THE ENTIRE |
| | SERVICE, PLEASE SUBMIT LOAD CALCS |
| | ACCORDINGLY. |
| | PLEASE KNOW, AUTOMATIC LOAD SHEDDING IS |
| | PERMITTED. |
| | 702,220,215.5 |
| | |
| | 2) NOTE: PLEASE SEE EXISTING SERVICE IS |
| | BEING SHOWN FEEDING ATS AND THEN BACK TO |
| | THE SAME SERVICE?? THISIS NOT CLEAR |
| | WHERE THIS FEEDER IS GOING AND WHERE THE |
| | DISCONNECTING MEANS IS? |
| | SERVICE AS SHOWN IS NOT CLEAR. |
| | MEANS OF DISCONNECT FROM GEN? |
| | GROUPING? |
| | 230.76,230.76,230.70,230.72, |
| | 225.31-225.39 |
| | PLEASE KNOW, ALL MAINS AND DISCONNECTING |
| | MEANS SHALL BE GROUPED. |
| | (BRKR ON GEN IS NOT INCLUDED WITH THE |
| | MEANS OF DISC.) |
| | PLEASE PROVIDE A LAY OUT FOR SERVICE AND |
| | LOCATION ON SITE. |
| | |
| | 3)NOTE: PLEASE PROVIDE THE OCP ON RISER |
| | FOR GEN. (IT IS NOTED IN SPECS AT |
| | 200A'S). |
| | |
| | 4) NOTE: PLEASE VERIFY THE GROUNDING |
| | ELECTRODE SYSTEM AT SERVICE. |
| | PLEASE SEE NOGE SYSTEM EXISTING OR |
| | OTHERWISE IS BEING SHOWN. |
| | 250.50,250.56, CWP? 2 GRND ROD? |
| | |
| | 5) NOTR: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT/MAINS. PLEASE SEE THAT |
| | NEW MAIN AND EXISTING SERVICE MUST BE |
| | RATED FOR THE AVAILABLE FUALT CURRENT |
| | FROM FPL AND FROM GENERATOR. |
| | 110.9, 215.5, NFPA-110 CHAPTER 7 |
| | |
| | |
| | PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT PLANS. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |