| Date |
Text |
| 2006-07-22 00:00:00 | ** UNSAT ** |
| | |
| | ** PLEASE SEE SOME INFORMATION FROM |
| | PREVIOUS REVIEW STILL NEEDS TO BE |
| | ADDRESSED ALONG WITH NEW COMMENT(S). |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC |
| | CHAPTER 13 AS PREVIOUSLY NOTED. PLEASE |
| | SEECOMPLIANCE WITH FBC CHAPTER 13 THEN |
| | PLEASE SEE THE FOLLOWING: |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3 |
| | PLEASE PROVIDE OVER-RIDES LOCATED AT THE |
| | ENTRANCE INTO SPACE WHERE OCCUPANT CAN |
| | CLEARLY SEE LIGHTING IN WHICH IS BEING |
| | CONTROLLED. |
| | PLEASE SEE SOME SYMBOLS ARE BEING SHOWN |
| | AT DOORS HOWEVER THESE ARE NOT CLEAR AS |
| | THEY COULD NOT BE LOCATED ON SYMBOL |
| | LIST? |
| | PLEASE SEE THAT TIME OF DAY SCHEDULING |
| | CAN BE CHOSEN BY OCCUPANT. ALL OVER |
| | RIDES IF ONMANUAL TIMED DEVICES MAY |
| | ONLY A MAX OF 4HRS AND OCCUPANT TYPE |
| | SENSORS MAY ONLY BE 30MINS. |
| | PLEASE INDICATE THE MAX 30MINS.' |
| | PLEASE SEE .1.3, AS SEPARATE SPACES |
| | CONTAINING FLOOR TO CEILING HEIGHT |
| | PARTITIONS REQUIRES CONTROLS AS NOTED. |
| | PLEASE SEE PREVIOUS NOTE WHICH THE |
| | ALLOWANCE AND DESIGN WATTAGE WAS IN |
| | QUESTION. PLEASE CLARIFY AS WATTAGE IS |
| | SHOWN OVER ALLOWANCE. |
| | 13-415.2.ABC.1, 415.2.C.1, 415.2.B.1 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS PLANS |
| | INDICATED THE PANEL "D" AS EXISTING |
| | ALTHOUGH NOTE MENTIONED NEW FEED FROM |
| | EXSTING PANEL "G". PLEASE SEE PANEL "D" |
| | IS NOW BEING SHOWN AS NEW. PLEASE SEE NO |
| | LOAD CALCUALTIONS WERE SUBMITTED FOR |
| | EXISTING PANEL "G" INDICATING NEW AND |
| | EXISTING LOADS BEING ADDED. |
| | PLEASE SUBMIT LOADS FOR PANEL "G" AND |
| | SIZE OF PANEL ETC TO VERIFY NEW ADDED |
| | LOADS. |
| | 220,215.5,215.3,230.42 ETC. |
| | FBC 106.1.2,106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE COLOR CODING FOR |
| | 277/480V SHALL BE BROWN, PURPLE, YELLOW. |
| | SHOWN WITH ORANGE FOR "B" PHASE, YET |
| | THISIS 277V NOT A "HIGH-LEG. |
| | PLEASE ADJUST. PLEASE SEE THAT THIS CAN |
| | BE REDLINED ALSO, AS NO 277V LIGHTING |
| | ETC IS BEING SHOWN. |
| | |
| | 4) NOTE: PLEASE VERIFY LOAD ON RECEPT |
| | CIRCUITS. PLEASE SEE SOME SHOWN AS |
| | 13.5VA, HOWEVER @180 VA PER KNOW RECEPT |
| | AND 9 ON EACH CIRCUIT THIS COMES UP TO |
| | 1620VA. |
| | PLEASE SEE 1,3,5,9,11, |
| | |
| | |
| | ** PLEASE SEE 605 FOR ALL MODULAR |
| | FURNITURE INSTALLATIONS.. |
| | |
| | ** PLEASE CALL TO GO OVER NOTE #1. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |