| 2006-06-20 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} INDICATE IF CIRCUITS SHOWN ARE NEW OR |
| | EXISTING. THE PANEL DESIGNATION "A", |
| | DOES NOT CORRESPOND TO ANY OF THE PANEL |
| | DESIGNATIONS(D G H F) SHOWN ON THE PLAN. |
| | LOCATE PANEL "A" ON THE PLAN. |
| | |
| | 2} THE ENGINEER OF RECORD SHALL INDICATE |
| | THE CERTIFICATE OF AUTHORIZATIONNUMBER |
| | ALONG WITH OTHER INFORMATION REQUIRED BY |
| | 61G15-23.002, FLORIDA ADMINISTRATIVE |
| | CODE, IN THE TITLE BLOCK. |
| | |
| | 3} SHOW DIAGRAMATICALLY COMPLIANCE WITH |
| | THE ENERGY CODE AS INDICATED IN THE |
| | "LIGHTING KEYNOTES". PLACE THE DEVICES |
| | ON THE DRAWING WHERE THE DESIGNER |
| | INTENDS FOR THEM TO BE INSTALLED. SEE |
| | THE REFERENCE TO THE " TORK #???" IS |
| | UNACCEPTABLE. |
| | |
| | 4} PLEASE SEE PAGE 3, LIGHTING POWER |
| | COMPLIANCE, ON FORM 400B, ATTACHED. THE |
| | OPEN OFFICE ENTRY WITH EFFECTIVE @ 1960 |
| | DOES NOT APPEAR TO COMPLY WITH THE |
| | ALLOWANCE , WHICH IS SHOWN @ 1903. |
| | |
| | 5} AN ELECTRICAL CONTRACTOR IS REQUIRED |
| | FOR THIS WORK AND MUST APPLY FOR A |
| | SEPERATE PERMIT SINCE NOT SIGNED ON WITH |
| | THE GC. |
| | |