2006-05-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 A GENERATOR (GEN-RES) PERMIT TYPE
 REQUIRES THAT THE TOTAL COST OF LABOR
 AND MATERIAL BE INCLUDED IN THE
 VALUATION. THIS WOULD BE ALL THE SERVICE
 EQUIPMENT AND THE PAD.
  
 THE LOAD AT 103 AMPS EXCEEDS THE
 GENERATOR OUTPUT AT 54 AMPS. SEE 702.5,
 NEC. IF LOAD SHEDDING IS INTENDED AS
 INDICATED, PLEASE SHOW HOW THIS IS TO BE
 ACCOMPLISHED WITH AN AUTOMATIC TRANSFER
 SWITCH.
  
 IT IS UNCLEAR HOW THE FEED FROM THE
 GENERATOR TO THE TRANSFER SWITCH IS
 BEING ROUTED. PLEASE SHOW THE LOCATION
 OF ALL SERVICE AN DGENERATOR EQUIPMENT
 ON A RISER DIAGRAM. SEE ARTICLE
 225.31-39 FOR DISCONNECT REQUIREMENTS.
  
 THE CONTRACTOR DOES NOT NEED TO SUBMIT
 THE ENTIRE OWNERS MANUAL.THE FOUR PAGE
 SPEC SHEETS CONTAIN ALL THE INFORMATION
 REQUIRED FOR REVIEW.
  