| Plan Review Notes For Permit 06040350 |
| Permit Number |
06040350 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-04 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | A GENERATOR (GEN-RES) PERMIT TYPE | | | REQUIRES THAT THE TOTAL COST OF LABOR | | | AND MATERIAL BE INCLUDED IN THE | | | VALUATION. THIS WOULD BE ALL THE SERVICE | | | EQUIPMENT AND THE PAD. | | | | | | THE LOAD AT 103 AMPS EXCEEDS THE | | | GENERATOR OUTPUT AT 54 AMPS. SEE 702.5, | | | NEC. IF LOAD SHEDDING IS INTENDED AS | | | INDICATED, PLEASE SHOW HOW THIS IS TO BE | | | ACCOMPLISHED WITH AN AUTOMATIC TRANSFER | | | SWITCH. | | | | | | IT IS UNCLEAR HOW THE FEED FROM THE | | | GENERATOR TO THE TRANSFER SWITCH IS | | | BEING ROUTED. PLEASE SHOW THE LOCATION | | | OF ALL SERVICE AN DGENERATOR EQUIPMENT | | | ON A RISER DIAGRAM. SEE ARTICLE | | | 225.31-39 FOR DISCONNECT REQUIREMENTS. | | | | | | THE CONTRACTOR DOES NOT NEED TO SUBMIT | | | THE ENTIRE OWNERS MANUAL.THE FOUR PAGE | | | SPEC SHEETS CONTAIN ALL THE INFORMATION | | | REQUIRED FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|