| Plan Review Notes For Permit 06040349 |
| Permit Number |
06040349 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-04 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: | | | | | | 1- CONTRACTOR WROTE DOWN ON TOP OF DADE | | | COUNTY NOA #02-0212.07 THAT SYSTEM TO BE | | | INSTALLED IS ON PAGE 19. SYSTEM ON PAGE | | | 19 IS FOR TILE UNDERLAYMENT APPLICATION | | | ONLY. THEREFORE, THIS SYSTEM DOESN'T | | | WORK. SPECIFY OTHER SYSTEM THAT WORKS | | | FOR PROPOSED INSTALLATION. COORDINATE | | | INFORMATION WITH ENGINEER. SEE COMMENT | | | #2 BELOW. | | | | | | 2- ENGINEER TO SPECIFY SPECIFIC SYSTEM | | | THAT HE'S REFERING TO IN ORDER TO VERIFY | | | COMPLIANCE WITH THE SPECIFIED DESIGN | | | PRESSURES AND ENHANCED FASTENING. PLEASE | | | SPECIFY PAGE OF APPROVED ASSEMBLY. | | | | | | 3- NOTICE OF COMMENCEMENT IS EXPIRED | | | AFTER 90 DAYS OF BEING RECORDED IF WORK | | | IS NOT STARTED. SEE SEC. 713.13(2) OF | | | FLORIDA STATUTES.NEED TO PROVIDE | | | RE-RECORDED NOTICE OF COMMENCEMENT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|