| 2006-05-23 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | 1.)SEE THE PREVIOUS LIST IN REGARDS TO |
| | THE WIND SPEED.SAME COMMENT STILL |
| | APPLIES.YOU CANNOT STATE THAT THE |
| | 3-SECOND GUST AND THE FASTEST MILE ARE |
| | 120.THEY ARE TWO DIFFERENT THINGS. SEE |
| | FBC1609.3.1 AND REVISE.PREVIOUS LIST |
| | STATED THAT CITY OF WPB IS IN THE 140 |
| | MPH, PLANS HAVE BEEN REVISED TO 120. |
| | YOU CANNOT DECLARE A WIND SPEED LESS |
| | STRINGENT THAT 140. |
| | |
| | 2.)MY PREVIOUS CORRECTION LIST MADE |
| | REFERENCE TO SOME OF THE OPTIONS ON THE |
| | PRODUCT APPROVAL BEING NON CODE |
| | COMPLIANT, IMPLYING THAT THERE WAS A |
| | COMPONENTS AND CLADDING PRESSURE ON THE |
| | PLAN I LOOKED AT BEFORE.THE PLANS NOW |
| | STATE "PLEASE FRANK I NEED THE WIND LOAD |
| | CALCULAITONS FOR THIS PROJECT, THANK |
| | YOU" PSF ON SHEET I-01.I AGREE, THIS |
| | IS DEFINITELY NEEDED. PLEASE PROVIDE SO |
| | THAT CODE COMPLIANCE CAN BE DETEREMINED. |
| | |
| | |
| | 3.)REMOVE REFERENCES TO EXPIRED CODES |
| | WHICH DON'T APPLY (HVHZ 2001 FBC). |
| | |
| | 4.)SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW FEE WILL BE CHARGED IF THE |
| | COMMENTS ARE NOT PROPERLY ADDRESSED A |
| | THIRD TIME.A COPY OF SHEET I-01 HAS |
| | BEEN RETAINED. |
| | |