2006-04-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SHEET I-01 REFERS TO ASCE7-98,
 CORRECT REFERENCE IS ASCE7-02, FBC35.
  
 3.)SHEET I-01 REFERS TO FBC2001.
 GOVERNING CODE IS FBC2004 EFFECTIVE
 OCOTBER 1, 2005.
  
 4.)WHEN DECLARING WIND SPEED IT SHOULD
 BE AS 3 SECOND GUST.YOU HAVE STATED
 THAT IT IS 3 SECOND GUST, FASTEST MILE.
 SEE FBC1609.3.1 AND REVISE.CITY OF WPB
 IS IN THE 140 MPH WIND ZONE.
  
 5.)THE PLANS INDICATE THAT SOME
 WINDOWS WILL BE SMALL MISSILE IMPACT.
 STATE THE DISTANCE FROM GRADE FOR THESE
 WINDOWS, FBC1609.1.4.
  
 6.)THE WASAU SUBMITTAL IS TO BE
 REVIEWED BY ENGINEER OF RECORD.THE
 SHOP DRAWINGS ARE NOT REQUIRED FOR
 PERMITTING.
  
 7.)WHAT IS THE CLASSIFICATION
 CATEGORY, I-01?YOU HAVE STATED THAT
 THIS IS IV, DO YOU MEAN BUILDING
 CONSTRUCTION TYPE?
  
 8.)ON THE PRODUCT APPROVAL, THERE ARE
 CHOICES AS TO THE CONSTRUCTION OF THE
 WINDOWS.CIRCLE THE ONE(S) YOU ARE
 USING AS NOT ALL OF THEM ARE COMPLIANT
 FOR ALL SIZES.IF YOU ARE USING
 DIFFERENT OPTIONS, INDICATE SUCH EITHER
 ON A SEPARATE SHEET OR BY NOTING ON THAT
 PAGE OF THE PRODUCT APPROVAL.
  
 9.)HAVE THE PRODUCT APPROVALS REVIEWED
 BY ENGINEER OF RECORD AFTER #8 IS DONE.
  
 10.)THE FLORIDA STATE PRODUCT
 APPROVALS SUBMITTED FL6116 IS NOT NEEDED
 AS A LOCAL PRODUCT APPROVAL HAS BEEN
 ISSUED WITH THE NOA.
  