Plan Review Notes
Plan Review Notes For Permit 06040239
Permit Number 06040239
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-27 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: PLANS HAVE BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AT THIS TIME.
  
 1. SHSTS H1.0, 3 & 4, WHEN SUBMITTING FOR
 PERMIT, IF THE DESIGN PROFESSIONAL IS A
 LANDSCAPE ARCHITECT, REGISTERED UNDER
 THE LAWS OF THIS STATE REGULATING THE
 PRACTICE OF LANDSCAPE ARCHITECTURE AS
 PROVIDED FOR IN CHAPTER 481 FS PART II,
 THEN HE OR SHE SHALL AFFIX HIS OR HER
 SEAL, SIGNATRUE, AND DATE TO SAID
 DRAWINGS. FS SECTION
 481.303(6)(A)(B)(C)(D). THE CERTIFICATE
 OF AUTHORIZATION NUMBER, (FIRM LICENSE
 NUMBER), AS WELL AS THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT IS
 REQUIRED ON EACH SHEET. FAC
 61G1-16.004(2)(6).
  
 2. ALL ARCHITECTURAL SHEETS. CERTIFICATE
 OF AUTHORIZATION NUMBER IS REQUIRED ON
 EACH SHEET AS WELL AS A DATED SEAL AND
 SIGNATURE OF THE DESIGN PROFESSIONAL.
 FAC 61G1-16.004(2)(5) & FS 481.2055.
  
 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY
 WITH SECTION 11-4.24.7 FAUCETS. PLEASE
 INDICATE COMPLIANCE ON DETAIL.
  
 4. SHT A104 GENERAL NOTES II(5)(C) GRAB
 BAR HEIGHTS SHALL BE 33" MIN. TO 36"
 MAX. PAGE 6.5 FHA DESIGN MANUAL.
  
 5. SHT A104. DETAIL 19 NEW CONST.
 ACCESSIBLE STALLS TO COMPLY WITH FIG.
 30E. A LAV IS REQUIRED IN THE STALL.
  
 6. SHT A104 GENERAL NOTES: II(4)(G) SINK
 SHALL HAVE FORWARD APPROACH PER SECTION
 11-4.24.5. SHOW ON DETAIL.
  
 7. SHT A201 DETAIL 07 SUPERIMPOSE THE
 CLEAR FLOOR SPACE FOR THE W/C AS
 REQUIRED ON PAGE 7.43.
  
 8 SHTS A201 THRU A205 INDICATE
 SPECIFICATION "A" OR "B" AS REQUIRED ON
 PAGES 7.34 & 7.35 FHA DESIGN MANUAL.
  
 9. SHT A202 UNIT PLAN GENERAL NOTES: #6
 ONLY 1ST FLOOR UNITS ARE REQUIRED TO
 COMPLY WITH FHA-98 DESIGN MANUAL
 REQUIREMENTS. PLEASE INDICATE WHERE IN
 THE FHA-98 DESIGN MANUAL IS THE
 REQUIREMENT FOR 7% ARE TO BE FULLY
 ADAPTABLE. PLEASE CLARIFY.
  
 10. SHT A203 AND A204 UNITS B1 & C1
 LOWER FLOOR REQUIRED TO MEET FHA-98
 DESIGN REQUIREMENTS 2ND BATHROOMS ARE
 EXEMPT ONLY FROM MANEUVERING AND CLEAR
 FLOOR SPACE IF SPECIFICATION "B" AND
 SHALL SHOW THE BACKING AS WELL AS THE
 SPACING FOR THE WATER CLOSET. (33"
 OPENING, 15"/18" BETWEEN THE FIXTURES).
 PLEASE SHOW ON PLANS. IF SPECIFICATION
 'A" THEN BATHROOM SHALL COMPLY WITH ALL REQUIREMENTS OF
 FHA DESIGN MANUAL.
  
 11. SHT A205 HDCP ACCESSIBLE UNIT PLAN
 NOTES LEGEND SHALL CHANGE REFERENCE
 STANDARD TO FHA-98 AMENDMENTS.
  
 12. SHT A205 HDCP ACCESS. UNIT PLAN
 NOTES LEGEND:NOTE #2 SINK SHALL BE
 ACCESSIBLE, NOT ADAPTABLE AS STATED.
 IF UNIT IS ACCESSIBLE, THEN IT SHALL BE
 BUILT ACCESSIBLE. SHOW CLEAR FLOOR
 SPACE.
  
 13. SHTS A302, A306, A307.1, A307.2,
 A310.1, A310.2 PLEASE CLARIFY WHAT COND.
 1, COND. 2, COND. 3, AND ACCESSIBLE
 @'C', @'E2', @'E1', @'D', 2 'M1', @ 'N',
 @ 'D2''K', @ 'F2' MEANS, OR WHERE THERE
 IS A LEGEND TO EXPLAIN THE MEANING OF
 THESE DESIGNATIONS. SECTION 106.1.1.
  
 14. SHT A304 SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY ROOF DRAINS.
 SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 & 1107 AND ALL SUBSECTIONS. SHOW THE
 SQUARE FOOTAGE FOR EACH AREA BEING
 DRAINED, ALONG WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO EACH AREA, AND ALL AREAS OF
 ROOFS THAT DRAIN ONTO THE AREAS FROM
 ABOVE.
  
 15. SHT A304 LOWER FLOOR INDICATES AREA
 DESIGNATED AS "B" OCCUPANCY, AND AREA
 DESIGNATED AS "A-3"OCCUPANCY. SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES FOR
 EACH OCCUPANCY PER TABLES 1004.1.2 AND
 403.1. A DRINKING FOUNTAIN IS REQUIRED
 IN EACH OCCUPANCY, AND A SERVICE SINK IS
 REQUIRED IN THE "A-3" OCCUPANCY. THERE
 ARE NO W/C'S, OR LAVS SHOWN IN ONE SPACE
 FOR LOWER FLOOR PLAN. PLEASE CLARIFY.
  
 16. SHT A306 BUILDING TYPE VI INDICATES
 A LEASING OFFICE, BUT SHT A101 BLDG.
 DATA INDICATES IT AS A COMMUNITY ROOM.
 PLEASE CLARIFY AND CORRELATE FLOOR PLANS
 AND BLDG. DATA. SECTION 106.1.1.
  
 17. SHT A700.1 FINISH SCHEDULE FOR
 LEASING OFFICE AND COMMUNITY RESOURCE.
 PLEASE INDICATE HOW PTD. GYP. BD. MEETS
 THE REQUIREMENT OF SECTION 1210.2.
  
 18. SHT A801 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTION, AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING IF THE DINKING FOUNTAIN IS NOT
 A "HI/LOW" TYPE.
  
 19. SHT A801 SINK SHALL BE ACCESSIBLE.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK.
  
 20. SHTS A802 DETAILS 04 & 09 INDICATE
 THE CENTERLINE OF THE W/C 18" OFF THE
 WALL, AND THE CENTERLINE OF THE LAV TO
 BE MIN. 15" OFF THE WALL (TO BE CENTERED
 ON THE 30" WIDTH OF THE CLEAR FLOOR
 SPACE). SECTIONS 11-4.16.2, 11-4.19.3
 AND FIG. 28.
  
 21. SHT A810 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AS WELL AS
 SECTION 11-4.1.3(10)(A). A SERVICE SINK
 IS REQUIRED FOR THE STORAGE OCCUPANCY.
 TABLE 403.1.
  
 22. SHT P201 PLAN KEY NOTE #2 INDICATES
 KITCHEN SINK ARM IS RUN UNDER THE SLAB,
 BUT THE 3S RISER DIAGRAM ON SHT P402
 INDICATES THE SINK ARM IS ABOVE THE SLAB
 PLEASE CLARIFY AND CORRELATE THE NOTES,
 FLOOR PLAN, AND RISER DIAGRAM. SECTION
 106.1.1.
  
 23 SHTS P301 THRU P310 PLAN KEY NOTES #7
 PRESSURE RELIEF VALVE IS INDICATED AS
 RUNNING UNDER THE SLAB. THE RELIEF VALVE
 DISCHARGE LINE SHALL NOT HAVE ANY
 TRAPPED SECTIONS PER SECTION 504.6.1.
  
 24. SHTS P303, P304, P305A, P307, P308A,
 P308B, P310 PLAN KEY NOTE #5 NOT FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 25. SHT P306 NO SANITARY PIPING SHOWN TO
 RISER 2S BY LEASING OFFICE, AND NO
 PIPING SHOWN TO RISER 5W. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 26. SHT P403 ALL WATER RISER DIAGRAMS,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE FROM RISER DIAGRAMS. WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9,
 (W/M'S, D/W'S, AND ICE MAKERS), SHALL BE
 SHOWN AND SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE", NOT IN
 THE CEILING. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
  
 28. SUBMIT A WATER RISER DIAGRAM FOR
 EACH BUILDING. SHOW ALL PIPE SIZES,
 VALVES. RISER CONNECTIONS, AND INDICATE
 BLDG. SHUTOFF VALVE AS WELL AS INDICATE
 THE RPZV BACKFLOW REQUIRED FOR EACH
 BUILDING. SECTIONS 106.1.5.1.3 AND
 SECTION 608.13.2.
  
 29. SUBMIT A STORM BLDG RISER ISOMETRIC
 AND RWL RISER DIAGRAM FOR BLDG IV. SHOW
 ALL PIPE SIZES AND INDICATE SQUARE
 FOOTAGE DRAINED. IF SECONDARY ROOF
 DRAINS ARE INSTALLED, SUBMIT A RISER
 ISOMETRIC DIAGRAM FOR THAT SYSTEM ALSO.
 IF OVERFLOW SCUPPERS ARE INSTALLED, THEY
 SHALL BE SIZED BY THE ENGINEER PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. THE SIZING OF THE OVERFLOW
 SCUPPERS CAN NOT BE DETERMINED WITH OUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE INDICATE ON THE PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved