| Date |
Text |
| 2006-04-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | NOTE: PLANS HAVE BEEN SUBMITTED FOR |
| | "PLAN REVIEW" ONLY AT THIS TIME. |
| | |
| | 1. SHSTS H1.0, 3 & 4, WHEN SUBMITTING FOR |
| | PERMIT, IF THE DESIGN PROFESSIONAL IS A |
| | LANDSCAPE ARCHITECT, REGISTERED UNDER |
| | THE LAWS OF THIS STATE REGULATING THE |
| | PRACTICE OF LANDSCAPE ARCHITECTURE AS |
| | PROVIDED FOR IN CHAPTER 481 FS PART II, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | SEAL, SIGNATRUE, AND DATE TO SAID |
| | DRAWINGS. FS SECTION |
| | 481.303(6)(A)(B)(C)(D). THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER, (FIRM LICENSE |
| | NUMBER), AS WELL AS THE PRINTED NAME OF |
| | THE PERSON SEALING THE DOCUMENT IS |
| | REQUIRED ON EACH SHEET. FAC |
| | 61G1-16.004(2)(6). |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. CERTIFICATE |
| | OF AUTHORIZATION NUMBER IS REQUIRED ON |
| | EACH SHEET AS WELL AS A DATED SEAL AND |
| | SIGNATURE OF THE DESIGN PROFESSIONAL. |
| | FAC 61G1-16.004(2)(5) & FS 481.2055. |
| | |
| | 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY |
| | WITH SECTION 11-4.24.7 FAUCETS. PLEASE |
| | INDICATE COMPLIANCE ON DETAIL. |
| | |
| | 4. SHT A104 GENERAL NOTES II(5)(C) GRAB |
| | BAR HEIGHTS SHALL BE 33" MIN. TO 36" |
| | MAX. PAGE 6.5 FHA DESIGN MANUAL. |
| | |
| | 5. SHT A104. DETAIL 19 NEW CONST. |
| | ACCESSIBLE STALLS TO COMPLY WITH FIG. |
| | 30E. A LAV IS REQUIRED IN THE STALL. |
| | |
| | 6. SHT A104 GENERAL NOTES: II(4)(G) SINK |
| | SHALL HAVE FORWARD APPROACH PER SECTION |
| | 11-4.24.5. SHOW ON DETAIL. |
| | |
| | 7. SHT A201 DETAIL 07 SUPERIMPOSE THE |
| | CLEAR FLOOR SPACE FOR THE W/C AS |
| | REQUIRED ON PAGE 7.43. |
| | |
| | 8 SHTS A201 THRU A205 INDICATE |
| | SPECIFICATION "A" OR "B" AS REQUIRED ON |
| | PAGES 7.34 & 7.35 FHA DESIGN MANUAL. |
| | |
| | 9. SHT A202 UNIT PLAN GENERAL NOTES: #6 |
| | ONLY 1ST FLOOR UNITS ARE REQUIRED TO |
| | COMPLY WITH FHA-98 DESIGN MANUAL |
| | REQUIREMENTS. PLEASE INDICATE WHERE IN |
| | THE FHA-98 DESIGN MANUAL IS THE |
| | REQUIREMENT FOR 7% ARE TO BE FULLY |
| | ADAPTABLE. PLEASE CLARIFY. |
| | |
| | 10. SHT A203 AND A204 UNITS B1 & C1 |
| | LOWER FLOOR REQUIRED TO MEET FHA-98 |
| | DESIGN REQUIREMENTS 2ND BATHROOMS ARE |
| | EXEMPT ONLY FROM MANEUVERING AND CLEAR |
| | FLOOR SPACE IF SPECIFICATION "B" AND |
| | SHALL SHOW THE BACKING AS WELL AS THE |
| | SPACING FOR THE WATER CLOSET. (33" |
| | OPENING, 15"/18" BETWEEN THE FIXTURES). |
| | PLEASE SHOW ON PLANS. IF SPECIFICATION |
| | 'A" THEN BATHROOM SHALL COMPLY WITH ALL REQUIREMENTS OF |
| | FHA DESIGN MANUAL. |
| | |
| | 11. SHT A205 HDCP ACCESSIBLE UNIT PLAN |
| | NOTES LEGEND SHALL CHANGE REFERENCE |
| | STANDARD TO FHA-98 AMENDMENTS. |
| | |
| | 12. SHT A205 HDCP ACCESS. UNIT PLAN |
| | NOTES LEGEND:NOTE #2 SINK SHALL BE |
| | ACCESSIBLE, NOT ADAPTABLE AS STATED. |
| | IF UNIT IS ACCESSIBLE, THEN IT SHALL BE |
| | BUILT ACCESSIBLE. SHOW CLEAR FLOOR |
| | SPACE. |
| | |
| | 13. SHTS A302, A306, A307.1, A307.2, |
| | A310.1, A310.2 PLEASE CLARIFY WHAT COND. |
| | 1, COND. 2, COND. 3, AND ACCESSIBLE |
| | @'C', @'E2', @'E1', @'D', 2 'M1', @ 'N', |
| | @ 'D2''K', @ 'F2' MEANS, OR WHERE THERE |
| | IS A LEGEND TO EXPLAIN THE MEANING OF |
| | THESE DESIGNATIONS. SECTION 106.1.1. |
| | |
| | 14. SHT A304 SHOW THE LOCATION OF ALL |
| | PRIMARY AND SECONDARY ROOF DRAINS. |
| | SUBMIT CALCULATION FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | & 1107 AND ALL SUBSECTIONS. SHOW THE |
| | SQUARE FOOTAGE FOR EACH AREA BEING |
| | DRAINED, ALONG WITH 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS |
| | ADDED TO EACH AREA, AND ALL AREAS OF |
| | ROOFS THAT DRAIN ONTO THE AREAS FROM |
| | ABOVE. |
| | |
| | 15. SHT A304 LOWER FLOOR INDICATES AREA |
| | DESIGNATED AS "B" OCCUPANCY, AND AREA |
| | DESIGNATED AS "A-3"OCCUPANCY. SUBMIT CALCULATIONS FOR |
| | MINIMUM FACILITIES FOR |
| | EACH OCCUPANCY PER TABLES 1004.1.2 AND |
| | 403.1. A DRINKING FOUNTAIN IS REQUIRED |
| | IN EACH OCCUPANCY, AND A SERVICE SINK IS |
| | REQUIRED IN THE "A-3" OCCUPANCY. THERE |
| | ARE NO W/C'S, OR LAVS SHOWN IN ONE SPACE |
| | FOR LOWER FLOOR PLAN. PLEASE CLARIFY. |
| | |
| | 16. SHT A306 BUILDING TYPE VI INDICATES |
| | A LEASING OFFICE, BUT SHT A101 BLDG. |
| | DATA INDICATES IT AS A COMMUNITY ROOM. |
| | PLEASE CLARIFY AND CORRELATE FLOOR PLANS |
| | AND BLDG. DATA. SECTION 106.1.1. |
| | |
| | 17. SHT A700.1 FINISH SCHEDULE FOR |
| | LEASING OFFICE AND COMMUNITY RESOURCE. |
| | PLEASE INDICATE HOW PTD. GYP. BD. MEETS |
| | THE REQUIREMENT OF SECTION 1210.2. |
| | |
| | 18. SHT A801 A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 AND ALL SUBSECTION, AS WELL AS |
| | SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING IF THE DINKING FOUNTAIN IS NOT |
| | A "HI/LOW" TYPE. |
| | |
| | 19. SHT A801 SINK SHALL BE ACCESSIBLE. |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | CLEAR FLOOR SPACE SHALL BE FORWARD |
| | APPROACH AND SHALL EXTEND A MAXIMUM OF |
| | 19" UNDERNEATH THE SINK. |
| | |
| | 20. SHTS A802 DETAILS 04 & 09 INDICATE |
| | THE CENTERLINE OF THE W/C 18" OFF THE |
| | WALL, AND THE CENTERLINE OF THE LAV TO |
| | BE MIN. 15" OFF THE WALL (TO BE CENTERED |
| | ON THE 30" WIDTH OF THE CLEAR FLOOR |
| | SPACE). SECTIONS 11-4.16.2, 11-4.19.3 |
| | AND FIG. 28. |
| | |
| | 21. SHT A810 A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 AND ALL SUBSECTIONS AS WELL AS |
| | SECTION 11-4.1.3(10)(A). A SERVICE SINK |
| | IS REQUIRED FOR THE STORAGE OCCUPANCY. |
| | TABLE 403.1. |
| | |
| | 22. SHT P201 PLAN KEY NOTE #2 INDICATES |
| | KITCHEN SINK ARM IS RUN UNDER THE SLAB, |
| | BUT THE 3S RISER DIAGRAM ON SHT P402 |
| | INDICATES THE SINK ARM IS ABOVE THE SLAB |
| | PLEASE CLARIFY AND CORRELATE THE NOTES, |
| | FLOOR PLAN, AND RISER DIAGRAM. SECTION |
| | 106.1.1. |
| | |
| | 23 SHTS P301 THRU P310 PLAN KEY NOTES #7 |
| | PRESSURE RELIEF VALVE IS INDICATED AS |
| | RUNNING UNDER THE SLAB. THE RELIEF VALVE |
| | DISCHARGE LINE SHALL NOT HAVE ANY |
| | TRAPPED SECTIONS PER SECTION 504.6.1. |
| | |
| | 24. SHTS P303, P304, P305A, P307, P308A, |
| | P308B, P310 PLAN KEY NOTE #5 NOT FOUND. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 25. SHT P306 NO SANITARY PIPING SHOWN TO |
| | RISER 2S BY LEASING OFFICE, AND NO |
| | PIPING SHOWN TO RISER 5W. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 26. SHT P403 ALL WATER RISER DIAGRAMS, |
| | AIR CHAMBERS ARE NOT APPROVED. PLEASE |
| | DELETE FROM RISER DIAGRAMS. WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9, |
| | (W/M'S, D/W'S, AND ICE MAKERS), SHALL BE |
| | SHOWN AND SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE", NOT IN |
| | THE CEILING. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 27. SUBMIT A BUILDING DRAIN SANITARY |
| | RISER DIAGRAM ISOMETRIC THAT REFLECTS |
| | THE FLOOR PLAN FOR EACH BUILDING. |
| | SECTION 106.1.5.1.3. SHOW ALL PIPE |
| | SIZES, RISER LOCATIONS, TRAPS, VENTS, |
| | AND DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. |
| | |
| | 28. SUBMIT A WATER RISER DIAGRAM FOR |
| | EACH BUILDING. SHOW ALL PIPE SIZES, |
| | VALVES. RISER CONNECTIONS, AND INDICATE |
| | BLDG. SHUTOFF VALVE AS WELL AS INDICATE |
| | THE RPZV BACKFLOW REQUIRED FOR EACH |
| | BUILDING. SECTIONS 106.1.5.1.3 AND |
| | SECTION 608.13.2. |
| | |
| | 29. SUBMIT A STORM BLDG RISER ISOMETRIC |
| | AND RWL RISER DIAGRAM FOR BLDG IV. SHOW |
| | ALL PIPE SIZES AND INDICATE SQUARE |
| | FOOTAGE DRAINED. IF SECONDARY ROOF |
| | DRAINS ARE INSTALLED, SUBMIT A RISER |
| | ISOMETRIC DIAGRAM FOR THAT SYSTEM ALSO. |
| | IF OVERFLOW SCUPPERS ARE INSTALLED, THEY |
| | SHALL BE SIZED BY THE ENGINEER PER |
| | SECTIONS 1101.7, 1107.3 AND TABLE |
| | 1106.7. THE SIZING OF THE OVERFLOW |
| | SCUPPERS CAN NOT BE DETERMINED WITH OUT |
| | REFERENCE TO THE DEFLECTION OF THE ROOF. |
| | PLEASE INDICATE ON THE PLANS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SUBMIT ONE SET OF PLANS FROM FIRST |
| | REVIEW FOR COMPARISON TO EXPEDITE 2ND |
| | REVIEW. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |