Plan Review Notes
Plan Review Notes For Permit 06040239
Permit Number 06040239
Review Stop M
Sequence Number 1
Notes
Date Text
2006-04-21 00:00:00* FOR PLAN REVIEW ONLY NOT FOR PERMIT *
 1) SEE PAGE M401, A/C SYSTEMS 3,4,5,6
 ARE SHOWING THE WRONG TONNAGE REFER TO
 MODEL NUMBERS.
 2) SEE PAGE M202 UNIT C1,B1,A1 RETURN
 AIR TRANSFER GRILL IS UNDER SIZED, SEE
 NOTE #12.
 3) SEE PAGE M202 UNIT A2, PROVIDE RETURN
 AIR TO LIVING ROOM, SEE NOTE #12.
 4) SEE PAGE M202 UNIT B1, CLOTHES DRYER
 VENT MUST TERINATE 4 FEET FROM DOOR, PER
 2004 FBC/M 501.2 .
 5) SEE PAGE M202 UNIT C1, B1 RETURN AIR
 TRANSFER GRILL IS IN THE WRONG LOCATION.
 6) SEE PAGE M201, M202, M203 NOT ALL
 SUPPLY AIR DUCTS ARE SIZED.
 7) SEE PAGE M203 UNIT B1, RETURN AIR
 TRANSFER GRILL TO MASTER BEDROOM IS
 UNDER SIZED, SEE NOTE #12.
 8) SEE PAGE M205 NEED TO SHOW OUTDOOR
 AIR CFM'S.
 9) SEE PAGE M205 NOT ALL SUPPLY AND
 RETURN AIR DUCTS ARE SIZED.
 10) SEE PAGE M202 RETURN AIR TRANSFER
 GRILL IS NOT LOCATED CORRECTLY.
 11) PROVIED COMBUSTION AIR FOR ALL GAS
 CLOTHES DRYERS AND SHOW ON MECHANICAL
 PLANS, PER 2004 FBC/M 701 .
 12)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
 13) PLEASE LOOK AT THE MECHANICAL PLANS
 AS THERE ARE RED NOTES WRITTEN ON THEM
 FOR CORRECTIONS THAT MAY NOT BE
 MENTIONED WITH-IN.
 14) PLEASE BE ADVISED CLOTHES DRYER
 VENTS APPEAR TO LONG, 25 FEET IS THE
 MAXIMUM LENGHT SEE 2004 FBC/M 504.6 .
 15) PLEASE SHOW HOW RETURN AIR IS
 GETTING BACK TO THE AIR HANDLER UNIT, ON
 MECHANICAL PLANS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.