| 2006-05-03 00:00:00 | ******DENIED****** |
| | |
| | PLAN REVIEW ONLY |
| | NOT FOR PERMIT AT THIS TIME |
| | |
| | 1) PLEASE NOTE THAT ALL NEW FIRE HYDRANT |
| | INSTALLATIONS SHALL BE WET AND OPERABLE |
| | PRIOR TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 2) PLEASE NOTE THAT IN ADDITION TO |
| | REFERENCED CODE EDITIONS, THE FIRE |
| | PREVENTION CODE, 2004 EDITION SHALL BE |
| | USED. |
| | |
| | 3) PLEASE NOTE THAT FIRE PLAN REVIEW |
| | WILL ONLY EFFECT RESIDENTIAL BUILDINGS |
| | WITH MORE THAN (3) UNITS UNDER ROOF. |
| | |
| | 4) FIRE DEPARTMENT ACCESS AND WATER |
| | SUPPLY TO COMPLY WITH NFPA 1, 2003 |
| | EDITION CHAPTER 18. |
| | |
| | 5) KNOX BOX ENTRY SYSTEM IS REQUIRED FOR |
| | LEASING BUILDING. |
| | |
| | 6) STAIRS SHALL COMPLY WITH APPLICABLE |
| | BUILDING CODES AND NFPA 101, 2003 |
| | EDITION SECTION 7.2.2. |
| | |
| | 7) HANDRAILS ARE REQUIRED ON BOTH SIDES |
| | OF STAIRS WITH EXCEPTION TO LIVING |
| | UNITS. |
| | |
| | 8) PLEASE VERIFY STAIR WIDTHS IN ALL |
| | LIVING UNITS. |
| | |
| | 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR HANDRAILS AND GUARDS. |
| | |
| | 10) ADDRESS NUMBERS ARE REQUIRED ON ALL |
| | BUILDINGS, AND SHALL MEET THE MINIMUM |
| | (3)" HEIGHT REQUIREMENT FOR RESIDENTIAL, |
| | AND (6)" HEIGHT FOR COMMERCIAL |
| | STRUCTURES. |
| | |
| | 11) MULTI-PURPOSE ABC TYPE FIRE |
| | EXTINGUISHERS ARE REQUIRED FOR ALL |
| | LEVELS OF EACH BUILDING. |
| | |
| | 12) THE TYPE 6 BUILDING TO MEET ALL |
| | REQUIREMENTS OF NFPA 101, SECTION |
| | 6.1.14.2.1, MULTIPLE OCCUPANCIES. |
| | |
| | 13) ELEVATORS TO COMPLY WITH ASME A17.1. |
| | |
| | 14) PLEASE PROVIDE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS IN TYPE 6 BUILDING. |
| | |
| | 15) IF BUILDINGS ARE NOT REQUIRED TO BE |
| | FIRE SPRINKLER PROTECTED IN ACCORDANCE |
| | WITH FLORIDA STATUTES AND BUILDING AND |
| | FIRE CODES, PLEASE REMOVE FIRE |
| | PROTECTION SCOPE AND NOTES FROM SHT |
| | P100. |
| | |
| | 16) ARE THERE ENOUGH FIRE HYDRANTS |
| | PLANNED TO MEET THE MAX. 300-500' |
| | DISTANCE REQUIREMENT? PLEASE BE SURE TO |
| | CLEARLY MARK ALL LOCATIONS AS SOME |
| | EXISTING LOCATIONS ARE HARD TO SEE ON |
| | DRAWINGS. |
| | |
| | 17) IT APPEARS THAT MORE EMERGENCY |
| | LIGHTING MAY BE REQUIRED IN CORRIDORS OF |
| | LEASING OFFICE. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |