2006-05-03 00:00:00******DENIED******
  
 PLAN REVIEW ONLY
 NOT FOR PERMIT AT THIS TIME
  
 1) PLEASE NOTE THAT ALL NEW FIRE HYDRANT
 INSTALLATIONS SHALL BE WET AND OPERABLE
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) PLEASE NOTE THAT IN ADDITION TO
 REFERENCED CODE EDITIONS, THE FIRE
 PREVENTION CODE, 2004 EDITION SHALL BE
 USED.
  
 3) PLEASE NOTE THAT FIRE PLAN REVIEW
 WILL ONLY EFFECT RESIDENTIAL BUILDINGS
 WITH MORE THAN (3) UNITS UNDER ROOF.
  
 4) FIRE DEPARTMENT ACCESS AND WATER
 SUPPLY TO COMPLY WITH NFPA 1, 2003
 EDITION CHAPTER 18.
  
 5) KNOX BOX ENTRY SYSTEM IS REQUIRED FOR
 LEASING BUILDING.
  
 6) STAIRS SHALL COMPLY WITH APPLICABLE
 BUILDING CODES AND NFPA 101, 2003
 EDITION SECTION 7.2.2.
  
 7) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF STAIRS WITH EXCEPTION TO LIVING
 UNITS.
  
 8) PLEASE VERIFY STAIR WIDTHS IN ALL
 LIVING UNITS.
  
 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND GUARDS.
  
 10) ADDRESS NUMBERS ARE REQUIRED ON ALL
 BUILDINGS, AND SHALL MEET THE MINIMUM
 (3)" HEIGHT REQUIREMENT FOR RESIDENTIAL,
 AND (6)" HEIGHT FOR COMMERCIAL
 STRUCTURES.
  
 11) MULTI-PURPOSE ABC TYPE FIRE
 EXTINGUISHERS ARE REQUIRED FOR ALL
 LEVELS OF EACH BUILDING.
  
 12) THE TYPE 6 BUILDING TO MEET ALL
 REQUIREMENTS OF NFPA 101, SECTION
 6.1.14.2.1, MULTIPLE OCCUPANCIES.
  
 13) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 14) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TYPE 6 BUILDING.
  
 15) IF BUILDINGS ARE NOT REQUIRED TO BE
 FIRE SPRINKLER PROTECTED IN ACCORDANCE
 WITH FLORIDA STATUTES AND BUILDING AND
 FIRE CODES, PLEASE REMOVE FIRE
 PROTECTION SCOPE AND NOTES FROM SHT
 P100.
  
 16) ARE THERE ENOUGH FIRE HYDRANTS
 PLANNED TO MEET THE MAX. 300-500'
 DISTANCE REQUIREMENT? PLEASE BE SURE TO
 CLEARLY MARK ALL LOCATIONS AS SOME
 EXISTING LOCATIONS ARE HARD TO SEE ON
 DRAWINGS.
  
 17) IT APPEARS THAT MORE EMERGENCY
 LIGHTING MAY BE REQUIRED IN CORRIDORS OF
 LEASING OFFICE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  