Plan Review Notes
Plan Review Notes For Permit 06040239
Permit Number 06040239
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-24 00:00:00REVIEW IN PROGRESS,
 MERRY PLACE
  
 ********** UNSAT *************
  
 ** PLEASE KNOW, PLANS WERE ONLY
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
  
 1)NOTE: WHEN SUBMITTING FOR PERMIT,
 PLEASE BE SURE PLANS ARE SIGNED , DATED
 AND SEALED AS REQUIRED UNDER FS 471.025,
 FAC 61G15-23.001 AND .002.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE
 THE FOLLOWING CODES: NFPA-70 2002,
 NFPA-72 2002.
 PLEASE ALSO SEE PLANS WHICH REFERENCE
 PROJECT AND SCOPE BEING LOCATED IN THE
 "CITY OF ATLANTA"?
 PLEASE ADJUST.
  
 3) NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION # ON TITLE BLOCK FOR
 JH&P.
 PLEASE SEE FS 481.219, AND FAC
 61G1-16.004.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE BE SURE TO SHOW ALL
 CIRCUITING ON PLANS FOR UNIT SNA FOR ALL
 COMMON AREAS. PLEASE SEE MISSING MANY
 AREAS.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/ EXT LTS. PLEASE SEE THAT THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT FEEDING THE LOCAL LIGHTING IN
 ANY ONE AREA.
 ** UNABLE TO REVIEW CERTAIN ITEMS FOR
 CODE COMPLIANCE AS CIRCUITING IS NOT
 SHOWN.
  
 5) NOTE: PLEASE SEE PLANS MENTIONS 90% ,
 PLEASE COMPLETE.
  
 6) NOTE: PLEASE SEE NFPA-72 11.8.3.5,
 FOR SD'S TO BE LOCATED A MIN OF 20' FROM
 COOKING APPLIANCES, UNLESS MEETING THE
 EXCEPTIONS AS SETFORH. SEE AND NOTE THIS REQUIREMENT
 AND EXCEPTION(S) ON PLANS
 WITH OTHER SD NOTES.
  
 7) NOTE; PLEASE SEE SOME MISSING GFI
 RECEPTS PER 210.52E FOR LOWER LEVEL
 UNITS.
  
 8) NOTE: PLEASE SEE UNIT A-2 SHOWS
 UPPER, HOWEVER DOES NOT SHOW LOWER? IS
 THERE A LOWER TO THIS UNIT?
  
 9) NOTE: PLEASE SEE PLANS INDICATE A
 BLDG TYPE IX ON CALCS AND RISER, HOWEVER
 COULD NOT LOCATE A BUILDING TYPE IX IN
 PLANS.?
 PLEASE CORRELATE.
  
 10) NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARANCES PERMITTED IN STORAGE AREAS.
 (UNDER STAIRS) FIX TYPE "H". PLEASE
 KNOW, WHEN SHELVING IS NOT SHOWN, A MIN
 18" IS ASSUMED AND LT SHALL MEET THE MIN CLEARANCES
 REQUIRED.
 PLEASE ADJUST.
  
 11) NOTE: PLEASE SEE 210.52 FOR SOME
 MISSING RECEPTS FOR WALL SPACE.
 (B1).
  
 12) NOTE: PLEASE VERIFY KITCHEN COUNTER
 SPACES AS SOME APPEAR TO CONTAIN 12" OR
 MORE AW/OUT A GFI.
 210.52C1.
  
 13) NOTE: PLEASE CLARIFY WHAT IS SHOWN
 ON PLANS AS A GAS WH BEING LOCATED ON TH
 OUTSIDE PORCH??"A1".
  
 14) NOTE: PLEASE SEE MISSING EGRESS
 CONTROL OF LTS ON SOME UNITS FOR UPPER
 TO LOWER LEVEL. (GRADE LEVEL ACCESS).
 210.70 (C-1).
  
 15) NOTE: PLEASE SHOW THE DISCONNECT
 LOCATIONS FOR ALL CU'S IT IS NOTED ON
 PLANS , HOWEVER LOCATIONS AND MIN
 CLEARANCES CAN NOT BE VERIFIED AT THIS
 TIME .
 440.11,110.26.
  
 16) NOTE: PLEASE SEE METER CENTER ON
 BLDG TYPE IV, APPEARS TO SHOW THIS IN
 STAIRS, ON STAIRS , OR UNDER STAIRS? IN
 EITHER CASE PLEASE INDICATE BY SHOWING AN
 ELEVATION DETAIL FOR THIS IS MOVE MC. 215.5,110.26
 PLEASE ALSO SEE BLDG TYPE 6, WHICH SHOWS
 CU'S DIRECTLY IN-FRONT OFMC>
  
 17) NOTE: PLEASE BE SURE TO SHOW ALL
 ROOM AND AREA DESIGNATIONS ON PLANS.
 UNABLE TO VERIFY SOME ITEMS NEEDED FOR
 CODE COMPLIANCE.
 215.5
  
 18) NOTE: PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR STAIR AND EGRESS
 HALLS.
 PLEASE SEE NFPA-101 7.8.1.3,7.9.2.2,
 WHICH REQUIRESA MIN-OF 10FT CANDLES
 (AVG) OF LT DURING NORMAL OPERATIONS AND
 1FT CANDLE MIN (AVG) UNDER EMERGENCY
 CONDITIONS.
 PLEASE SEE THIS INCLUDES BLDG TYPE VI.
 AND STAIRS IN OTHER BUILDINGS WITH
 COMMON AREA GRADE LEVEL ACCESS.
 ( THIS IS NOT FOR INSIDE UNITS).
  
 19) NOTE: PLEASE SEE FBC CHAPTER 13 FOR
 LIGHTING CONTROLS REQUIRED IN BLDGS
 GREATER THAN 5 SQ FT. (TYPE VI).
 PLEASE PROVIDE INFORMATION ON SYSTEM
 BEING INSTALLED, SCHEDULE, TYPE OF
 DEVICES ETC.
 PLEASE SEE 13-415.1.ABC.1.1, .2, .3 ETC.
  
 20) NOTE: PLEASE SEE 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS.
 PLEASE SEE BREAK AREA WHICH MAY BE
 CONSIDERED AS APPLIANCES ETC MAY BE
 INSTALLED.
  
 21) NOTE: PLEASE DETAIL LOAD
 CALCULATIONS FOR DERATING FACTORS BEING
 TAKEN.
 PLEASE SEE 220.32.
  
 22) NOTE: PLEASE SEE SEC'S FOR MC'S
 7,9,10, PLEASE SEE MINSIZES REQUIRED
 MAY BE SIZED TO NEXT SIZE OCP, HOWEVER
 PLEASEKNOW, THE CONDUCTORS SHALL MEET
 THE MIN LOADS IN LOAD CALCULATIONS.
 PLEASE SEE LOADS AFTER ALL DERATING,
 EXCEED THE RATING OF CONDUCTORS
 INDICATED.
 240.3,240.4,310.16.
  
 23) NOTE: PLEASE SEE CORRELATE ALL NOTES
 WITH METER CENTER RISERS.
 PLEASE SEE "NOTE #7" AS LISTED INDICATES
 A 225A MCB ON A 200A METER.??
 PLEASE ALSO SEE OTHER AREAS WHERE THE
 FEEDERS ARE ALSO NOTED WITH THIS SAME
 NOTE #7??
 215.5
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS BEFORE RESUBMITTING
 PLANS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-20 00:00:00REVIEW IN PROGRESS. WILL PROCEED TO "F"
 STATUS.
 NOTES TO FOLLOW ON 4/25