2006-06-21 00:00:00BUILDING REVIEW CHECKLIST FOR PLAN
 REVIEW ONLY:
 1- PROVIDE THE FOLLOWING WHEN APPLYING
 FOR BUILDING PERMITS:
 A)NOTICE OF COMMENCEMENT FOR EACH
 BUILDING.
 B) RECEIPT OF PAID IMPACT FEES AND
 PLANS STAMPED WITH IMPACT FEES STAMP BY
 PALM BEACH COUNTY FOR EACH BUILDING.
 C) DRAWINGS ARE 90% COMPLETE. NEED
 DRAWINGS COMPLETE TO 100%.
 D) ARCHITECT TO PROVIDE ALL INFORMATION
 IN THE TITLE BLOCK AS REQ'D BY CHAPTER
 481 FLORIDA STATUTE AND 61G1-16.004 FAC.
 E) ENGINEER'S TO PROVIDE ALL INFORMATION
 AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND 61G15-23.002 FAC.
 F) SOIL TEST REPORT FOR EACH BUILDING.
 G) ENERGY CALCULATIONS FOR EACH BLDG.
 H) SIGNED AND SEALED SURVEYS.
  
 2- PROVIDE INTERIOR FINISHES SCHEDULE
 INDICATING TYPE OF FINISH. SEE TABLE
 803.5 FBC 2004.
  
 3- PROVIDE COMPLETE SITE PLAN WITH
 DIMENSIONS SHOWING BUILDING SEPARATION
 TO VERIFY COMPLIANCE WITH TABLES 601,
 602 FBC FOR FIRE RESISTANCE AND TABLE
 704.8 FBC 2004 FOR OPENINGS ALLOWED.
  
 4- SHEET A100: A) CIVIL DRAWINGS ARE
 DONE BY ISBELL ENGINEERING OR EAST BAY
 GROUP. SEE GENERAL NOTE #1 AND FOR
 REFERENCE ONLY NOTE. REVISE AS REQUIRED.
 B) NEED NORTH ARROW.
 C) SHOW H/C TOTAL NUMBER OF PARKING
 SPACES AND SIZE FOR EACH BUILDING
 ACCORDING TO FAIR HOUSING ACT & CHAPTER
 11 OF FBC.
 D) BUILDING TYPE IV FOOTPRINT DOESN'T
 MATCH PLANS. REVISE AS REQUIRED. CHECK
 FOOTPRINT OF ALL OTHER BUILDING TYPES.
 E) SHOW ACCESSIBLE ROUTE FROM PARKING
 SPACE TO ENTRANCE TO EACH UNIT, LEASING
 OFFICE AND COMMUNITY BUILDING. PROVIDE
 DETAILS.
  
 5- SHEET A101: A) REVISE CODE
 INFORMATION. THERE IS NOT ENERGY CODE
 2004 FLORIDA BUILDING CODE (CHAPTER 27).
 SEE CHAPTER 13 FBC 2004.
 B) THERE IS NOT 1982 CITY OF ATLANTA
 ZONING ORDINACE. CHECK WITH CITY OF WEST
 PALM BEACH ZONING DEPARTMENT FOR CORRECT
 ZONING REFERENCE.
 C) FLORIDA ACCESSIBLE REFERENCES ARE
 FLORIDA BUILDING CODE CHAPTER 11 AND
 FAIR HOUSING ACT REVISED IN APRIL OF
 1998.
 D) THERE IS NOT PARKING INFORMATION
 SUBMITTED. NEED GENERAL PARKING AND H/C
 PARKING. SEE FAIR HOUSING AND CHAPTER 11
 FBC 2004 FOR REQ'D H/C SPACES AND SIZES.
 E) REVISE TYPE IV AND TYPE VI BUILDING
 TO MATCH WHICH ONE IS USED FOR COMMUNITY
 ROOM AND WHICH ONE FOR LEASING OFFICE.
 F) PROVIDE CALCULATIONS SHOWING AREA
 INCREASE.
 G) ALLOWABLE AREA/HEIGHT CALCULATIONS:
 CLARIFY NOTE FOR R-2: NO INCREASE BASED
 ON SPRINKLER PROTECTION?. ONLY BUILDING
 TO HAVE SPRINKLER IS THE MIXED BUILDING
 TYPE VI, WHICH HAVE THE LEASING OFFICE
 AND APARTMENTS AT BOTH SIDES. THE OTHER
 BUILDING TYPES ARE NOT SPRINKLERED.
 H) SPECIFY TOTAL BUILDING AREA FOR EACH
 COMPLETE BUILDING TYPE. BRAKE DOWN INTO
 A/C AREAS AND NON A/C AREAS (EG:
 BALCONIES AND ENTRY PORCHES) TO VERIFY
 BUILDING AREAS AND FOR PERMIT VALUATION.
 D) ACCESSIBILITY NOTES: THERE IS NOT
 SECTION 1107.5.4, EX 1. REVISE AS REQ'D.
 I) REVISE DWELLING UNIT TYPES CALCS. ALL
 UNITS IN GROUND FLOOR NEED TO COMPLY
 WITH FAIR HOUSING ACT.
 J) PROVIDE VENTILATION CALCULATIONS AND
 PLANS TO SHOW DETAILS & VENTS LOCATION.
 K) FIRE RATING REQUIREMENTS: PROVIDE
 ONLY THE INFORMATION THAT PERTAINS TO
 THIS PROJECT TO AVOID CONFUSION AND
 FACILITATE THE REVIEW PROCESS.
 L) PROVIDE CALCULATIONS FOR OCCUPANT
 LOAD IN ASSEMBLY BUILDING USING 5 SF,
 WHICH IS THE WORST CASE SCENARIO. TABLE
 1004.1.2 FBC 2004.
  
  
 6- SHEET A103: A) PROVIDE ONLY THE
 DETAILS THAT APPLY TO THIS PROJECT TO
 AVOID CONFUSIONS AND TO FACILITATE
 REVIEW PROCESS.
 B) DETAIL 19: WHERE DOES THIS DETAIL
 APPLY TO.SEE FIGURE 38 OF CHAPTER 11
 FBC 2004 FOR MAX. REACH HEIGHT.
  
 7- SHEET A104: A) PROVIDE ONLY THE
 DETAILS THAT APPLY TO THIS PROJECT.
 B) WHERE ARE THE DRINKING FOUNTAINS AND
 WATER COOLERS IN PLANS.
 C) COMMON USE FACILITIES NOTE #2A):
 CLARIFY MAX. LOW PROFILE.
  
 8- SHEET A110: UL FIRE ASSEMBLY -L528.
 THERE ARE 13 DIFERENT SYSTEMS.
 INDICATE WHICH SPECIFIC SYSTEMIS THE
 ONE GOING TO BE INSTALLED TO CHECK
 COMPLIANCE IN PLANS.
  
 9- SHEET A201: A) SPECIFY SAFETY GLASS
 AS REQUIRED BY SEC. R308.4 2004 FOR:
 * BATHROOM WINDOW.
 ** WINDOWS BY THE STAIRWAY ON END UNITS
 (NOTE: THIS APPLIES TO ALL UNIT TYPES
 THAT ARE AT THE END OF THE BUILDING AND
 HAVE WINDOWS BY THE STAIRWAY).
 *** WINDOW NEXT TO ENTRY DOOR AND
 WINDOW NEXT TO BALCONY DOOR.
 B) CLARIFY WHAT ARE THE GRAY SHADED
 WALLS FOR?
 C) CLEARLY IDENTIFY AREAS TO HAVE GRAB
 BARS REINFORCEMENT. DIMENSIONS ETC.
  
 10- A) SPECIFY ATTIC ACCESS FOR ALL 2ND
 FLOOR UNITS. SEC. R807 2004.
 B) SPECIFY ATTIC ACCESS FOR 2ND FLOOR
 LEASING OFFICE. SEC. 1209 FBC 2004.
  
 11- SHEET A202: A)PLANS ARE NOT LEGIBLE.
 THEY HAVE OVERLAPPING INFORMATION.
 REVISE AS REQUIRED.
 B) UNIT PLAN GENERAL NOTES: REVISE NOTE
 #6. ALL GROUND UNITS MUST COMPLY WITH
 THE FAIR HOUSING ACT.
 C) REVISE NOTE #17. OUTLETS TO BE NOT
 "LOWER" THAN 15", NOT "HIGHER" THAN 15".
 D) WHAT ARE THE GRAY SHADED WALLS FOR?
 THERE IS NOT LEGEND FOR THIS WALLS.
 (NOTE: THIS APPLIES TO ALL UNIT TYPES
 THROUGHOUT ALL DRAWINGS).
 E) SPECIFY SAFETY GLASS FOR ALL D
 WINDOWS.
  
 12- SHEET A203: A) THE ACCESSIBLE UNIT
 IS THE LOWER ONE, NOT THE UPPER UNIT.
 REVISE AS REQUIRED.
 B) CLEARLY SPECIFY ALL AREAS TO HAVE
 REINFORCEMENT FOR GRAB BARS IN ALL
 BATHROOMS AND PROVIDE REINFORCEMENT
 DETAIL. (NOTE: THIS APPLIES TO ALL
 BATHROOMS IN ALL UNIT TYPES THROUGHOUT
 ALL DWGS). SPECIFY DIMENSIONS ETC.
 C) SPECIFY SILL HEIGHT OF WINDOW B TO
 VERIFY COMPLIANCE WITH SAFETY GLAZING.
 D) SPECIFY SAFETY GLAZING FOR WINDOW
 NEXT TO THE ENTRY DOOR AND WINDOW NEXT
 TO THE BALCONY DOOR. (NOTE: THIS APPLIES
 TO ALL UNIT TYPES SHOWN THROUGHOUT ALL
 DRAWINGS). SEC. R308.4 2004.
 E) SHOW DETAIL AT GROUND UNIT ENTRANCE
 SHOWING COMPLIANCE WITH ACCESSIBLE ROUTE
 AND ENTRY THRESHOLD HEIGHT. (NOTE: THIS
 APPLIES TO ALL GROUND UNITS AND TO
 ENTRANCE TO LEASING OFFICE AND COMMUNITY
 ROOMS). SEE FAIR HOUSING ACT AND CHAPTER
 11 FBC 2004.
  
 13- SHEET A204: CLOSET DOORS FOR
 SECONDARY BEDROOMS DON'T COMPLY WITH
 FAIR HOUSING ACT. SEE PAGE 3.15 FAIR
 HOUSING ACT. AND COMMENTS ON PLANS.
  
 14- SHEET A205: A) SHOW THE 60"X60"
 CLEAR FLOOR SPACE AT UNIT ENTRY DOORS AS
 SPECIFIED ON H/C ACCESSIBLE UNIT NOTE
 #13. (NOTE: THIS APPLIES TO ALL UNIT
 TYPES SHOWN THROUGHOUT ALL DRAWINGS).
 B) UNIT C1: CLOSET DOORS FOR SECONDARY
 BEDROOMS DON'T COMPLY WITH FAIR HOUSING
 ACT. SEE PAGE 3.15 FHA.
  
 15- PROVIDE SECTION DETAIL AND SPECS FOR
 1HR FIRE RATED ASSEMBLY AT STAIRWAY FOR
 HORIZONTAL TENANT SEPARATION.
  
 16- A) ALL ROOF PLANS TO SHOW
 FIREBLOCKING BETWEEN UNITS.
 B) ALL ROOF PLANS TO SHOW ATTIC
 VENTILATION CALCULATIONS AND VENTS SIZE
 AND LOCATION.
  
 17- SHEET A302 ROOF FRAMING PLAN:
 SPECIFY 2 LAYERS OF UNDERLAYMENT FOR
 ROOF PITCH OF 2.25:12 AS REQUIRED BY
 SEC. R905.2.7 2004.
  
 18- SHEET A304: A) ROOF PLAN: SHOW ROOF
 DRAINS.
 B) PROVIDE COMPLETE DETAILS/SPECS FOR
 WOOD TRELLIS.
 C) UPPER FLOOR PLAN IS NOT LEGIBLE.
  
 19- SHEET A404: A) REVISE ELEVATION
 ORIENTATION. SEE SURVEY OR SITE PLAN FOR
 CORRECT ORIENTATION. NORTH, SOUTH ETC.
 B) ELEVATION #19 TO MATCH FLOOR PLAN.
 SEE COMMENTS ON PLANS.
 C) ELEVATIONS 04 AND 09: PROVIDE MORE
 INFORMATION TO DESCRIBE MATERIALS ON 2ND
 FLOOR OPENINGS BY STAIRWAY. SEE COMMENTS
  
 20- SHEET A406: A) MISSING ONE
 ELEVATION.
 B) ELEVATION 09 IS MISSING INFORMATION.
 EG: LEASING OFFICE BEHIND.
 C) ELEVATION 11 AND 16 DON'T MATCH.
 CHECK TIE BEAM ELEVATION FOR SECOND
 FLOOR AT LEASING OFFICE AREA.
 D) SHINGLES CAN'T BE INSTALLED OVER 33'
 MEAN ROOF HEIGHT BUILDING. SEE
 LIMITATIONS ON PRODUCT APPROVAL.
 THEREFORE, LEASING OFFICE CAN'T HAVE
 SHINGLES.
 E) SPECIFY SIZE OF WINDOWS AT "DORMER"
 WITH CLERESTORY WINDOWS. SEE COMMENTS.
 F) CHECK TIE BEAM ELEVATION FOR STAIRS
 #2 AT LEASING OFFICE.
  
 21- SHEET A500: A) DETAIL 06 AND 17 NEED
 TO MATCH. CHECK # OF GYP. BD. LAYERS.
 B) DETAIL 11 AND 17 NEED TO MATCH. T&G
 OR PLYWOOD DECKING. REVISE AS REQUIRED.
 C) DETAIL 17: FLOOR ASSEMBLY L-528
 DOESN'T INCLUDE BATT INSULATION AS SHOWN
 ON DETAIL. REVISE AS REQUIRED. PROVIDE
 UL ASSEMBLY THAT INCLUDES INSULATION.
 D) WHERE IS ASSEMBLY UG05 SPECIFIED ON
 DETAIL 17. SEE COMMENTS ON PLANS.
 E) ROOF ASSEMBLY RC-2601 SPECIFIED ON
 DETAIL 17 DOESN'T INCLUDE INSULATION.
 REVISE AS REQUIRED. NEED ASSEMBLY THAT
 IS TESTED WITH INSULATION.
 F) PROVIDE DETAIL/SPECS FOR FIRE RATED
 ASSEMBLY UNDER STAIRS.
 G) SHOW FIREBLOCKING WHERE REQUIRED BY
 SEC. R602.8 2004.
  
 22- SHEET A501: A) WALL SECTIONS TO
 MATCH STRUCTURAL PLANS. SEE STRUCTURAL
 PLANS FOR TRUSSES ORIENTATION.
 B) WALL SECTION 19:
 * BALCONY IS BUILD WITH CONCRETE. SEE
 STRUCTURAL DRAWINGS.
 ** SEE STRUCTURAL DWGS FOR RAKED BEAM
 SPECS. AND REVISE AS REQUIRED.
 C) PROVIDE COMPLETE DETAILS, SPECS AND
 DIMENSIONS FOR BALCONY HANDRAIL. SECTION
 R312 2004 RESIDENTIAL CODE.
 D) SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION WHERE REQUIRED BY SEC. R602.8
  
 23- SHEET A502: A) PROVIDE COMPLETE
 STRUCTURAL DETAILS FOR ROOF OVERHAND ON
 WALL SECTION 16.
 B) SPECIFY FIREBLOCKING LOCATION AND
 MATERIAL IN ALL WALL SECTIONS.
 C) WALL SECTION 18:
 * BALCONY CONSTRUCTION TO MATCH
 STRUCTURAL DRAWINGS.
 ** NOTE REFERING TO FLOOR ASSEMBLY IS
 CALLING FOR ROOF. REVISE TYPO.
 *** PROVIDE COMPLETE STRUCTURAL DETAILS
 AND SPECS FOR CONSTRUCTION OF
 OVERLAPPING "DORMER" WITH CLERESTORY
 WINDOWS.
 **** PROVIDE COMPLETE DETAIL/SPECS FOR
 ROOF BEAM AT BALCONY. NOTE: STRUCTURAL
 DWGS CALL FOR RAKED BEAM. THIS IS NOT A
 RAKED BEAM. REVISE BOTH DRAWINGS TO
 MATCH.
  
 24- SHEET A510: A) SPECIFY FIREBLOCKING
 MATERIAL AND LOCATION IN ALL SECTIONS.
 B) WHERE IS DETAIL 11/A500 SPECIFIED
 ON WALL SECTION 19?
 C) PROVIDE COMPLETE DETAILS/SPECS FOR
 BALCONY GUARDRAIL AS REQUIRED BY SEC.
 1012 FBC 2004.
 D) PROVIDE SPECIFICATIONS FOR WINDOWS
 IN BALCONY AREA. PLANS DON'T PROVIDE ANY
 OF THIS INFORMATION.
 E) PROVIDE COMPLETE DETAIL/SPECS FOR
 WOOD BRAKET. SEE WALL SECTION 19.
  
 25- SHEET A520: A) NEED TO PROVIDE 2 HR
 FIRE RATED FLOOR ASSEMBLY AS REQUIRED BY
 TABLE 302.3.2 FBC 2004.
 B) PROVIDE COMPLETE DETAILS/SPECS FOR
 WOOD TRELLIS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 26- SHEET A601: A) REVISE RISER AND
 TREAD DIMENSIONS TO COMPLY WITH SEC.
 R311.5.3.2 2004 RESIDENTIAL CODE.
 B) PROVIDE DETAILS/SPECS FOR
 INSTALLATION OF CANOPY AB0VE ENTRY DOOR.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 27- SHEET A602: A) DWGS ARE INCOMPLETE.
 ALSO, SHOW HANDRAILS AND TREAD AND
 RISER DIMENSIONS.
 B) DRAWINGS TO MATCH STRUCTURAL DWGS.
 C) CLARIFY CONSTRUCTION STAIRS. WOOD
 OR CONCRETE. SEE STRUCTURAL DRAWINGS.
  
 28- SHEET A603: A) REVISE TREAD AND
 RISER DIMENSIONS TO COMPLY WITH SECTION
 R311.5.3.2.
 B) PROVIDE COMPLETE DIMENSIONS. EG:
 STAIR WIDTH.
  
 29- SHEET A604: A) NEED ALL DIMENSIONS
 TO CHECK COMPLIANCE WITH CHAPTER 11 FBC
 2004.
 B) REVISE NOSING ON DETAIL 02 TO COMPLY
 WITH SEC. 11-4.9.3 FBC 2004.
 C) HANDRAILS ENDS TO COMPLY WITH
 SECTION 11-4.9.4 FBC 2004.
  
 30- SHEET A700.1: A) DETAIL 02: SEE
 FIGURE 38 CHAPTER 11 FBC 2004 AND REVISE
 AS REQUIRED.
 B) ROOM FINISH SCHEDULE: CLARIFY WHERE
 ARE THE MIRRORS ON STAIR #1.
  
 31- SHEET A701.1: A) DETAIL 01: SPECIFY
 MULLION FASTENERS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 B) WINDOW DETAILS: SPECIFY FASTENERS
 FOR 2X BUCK. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 C) WINDOW SCHEDULE: CLARIFY WHICH
 BUILDING HAS WINDOW G?. SEE PLANS. ALSO,
 SIZE DOESN'T MATCH SIZE SHOWN ON WINDOW
 ELEVATIONS AT BOTTOM OF PAGE.
  
 32- SHEET A702.1: A) SPECIFY FASTENERS
 FOR MULLION ABOVE DOOR. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 B) REVISE THRESHOLD DETAILS TO COMPLY
 WITH CHAPTER 11 FBC 2004 AND FAIR
 HOUSING ACT FOR ACCESSIBLE UNITS.
  
 33- SHEET A703: DETAIL 03: WHERE IS
 DETAIL XX/XXXX?.
 B) DETAIL 13: WHERE IS DETAIL XX/XXXX.
  
 34- SHEET A704: REVISE DETAIL 18. SEE
 STRUCTURAL PLANS FOR TYPE OF FLOOR
 CONSTRUCTION.
  
 35- SHEET A705: A) DETAIL 02: REVISE
 FASTENER SPACING.
 B) DETAIL 03: REVISE SHINGLES
 INSTALLATION. SEE PRODUCT APPROVAL.
 C) REVISE DETAIL 17. SEE RIDGE VENT
 PRODUCT APPROVAL.
 D) DETAIL 18: SPECIFY THICKNESS OF OSB
 DRAFTSTOP.
 E) SPECIFY ATTIC VENTILATION SIZE AND
 LOCATION. SEC. R806.
  
 36- SHEET A706.1: REVISE CLEARANCE
 REQUIRED BETWEEN HOOD AND RANGE ON
 DETAIL 08. SEE HOOD SPECIFICATIONS.
  
 37- SHEET A707: A) PROVIDE DIMENSIONS ON
 ELEVATIONS WHERE REINFORCING IS
 REQUIRED FOR GRAB BARS.
 B) PROVIDE COMPLETE BLOCKING
 DETAILS/SPECS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 38- SHEET A801: A) SPECIFY SAFETY GLASS
 FOR WINDOW NEXT TO DOOR IN THEATRE.
 SEC. 2406 FBC 2004.
 B) PROVIDE ATTIC ACCESS. SEC. 1209.2
 FBC 2004.
 C) STAIR #1: WIDTH OF STAIRS CAN'T BE
 REDUCED. REVISE AS REQUIRED.
 D) SHOW WINDOWS ON 2ND FLOOR PLAN BY
 MULTI-PURPOSE ROOM.
 E) PROVIDE COMPLETE DETAILS/SPECS FOR
 ELEVATOR. SEC 106.1.2 CITY AMENDMENTS TO
 FBC AND CHAPTER 11 FBC 2004.
 F) COMPLETE INFORMATION AT BALCONY
 AREA. MISSING GUARDS, ETC.
 G) NEED MAX. OCCUPANT LOAD SIGN.
  
 39- SHEET A802: A) COMPLETE DRAWINGS TO
 100%. PROVIDE DIMENSIONS, THRESHOLD,ETC.
 B) COMPLETE DETAIL 04. GRAB BARS, ETC.
 C) HANDRAIL DON'T COMPLYWITH SEC.
 11-4.9.4 FBC 2004.
 D) PROVIDE CORRECT NAME FOR EACH STAIR.
 STAIR #1 ND #2. BOTH ARE NAMED STAIR #1.
 REVISE AS REQUIRED.
  
 40- SHEET A810: A) NEED MAX. OCCUPANT
 LOAD SIGN.
 B) SPECIFY SAFETY GLASS FOR WINDOWS
 NEXT TO DOORS. SEC. 2406.3 FBC 2004.
 C) SHOW THRESHOLD FOR H/C ACCESS.
 D) DETAIL 09: PROVIDE COMPLETE
 INFORMATION INCLUDING, GRAB BARS SIZES,
 LOCATION AND REINFORCEMENT.
 E) WHERE IS THE DOOR SCHEDULE FOR ENTRY
 DOORS.
  
 41- SHEET S-1.1: A) 90% COMPLETE
 DRAWINGS. PROVIDE 100%COMPLETE DWGS.
 THIS COMMENT APPLIES TO ALL STRUCTURAL
 DRAWINGS.
 B) GROUND UNITS NEED TO BE ACCESSIBLE.
 REVISE DROP AT ENTRY OF UNITS.
 COORDINATE WITH ARCHITECTURAL DRAWINGS.
 ***NOTE: THIS COMMENT APPLIES TO ALL
 BLDG TYPES. REVISE ALL DRAWINGS WITH
 GROUND UNITS AS REQUIRED.
 C) 2ND FLOOR FRAMING PLAN: REVISE
 CONNECTOR SPECIFIED ON NOTE #1 FOR
 GIRDER TRUSS. NEED TO SPECIFY A WOOD TO
 MASONRY CONNECTOR. CONNECTOR SPECIFIED
 IS A WOOD TO WOOD CONNECTOR.
 ***NOTE: THIS COMMENT APPLIES TO ALL 2ND
 FLOOR FRAMING PLANS IN ALL BUILDING
 TYPES. REVISE THIS NOTE IN ALL DRAWINGS
 AS REQUIRED.
  
 42- SHEET S-1.2. ROOF FRAMING PLAN.
 REVISE TYPE OF BEAM SPECIFIED FOR LITTLE
 FLAT ROOF ABOVE SOME ENTRY AREAS. FLAT
 ROOF DON'T HAVE RAKED BEAM TB-1. THIS
 COMMENT APPLIES TO ALL BUILDING TYPES
 WITH FLAT ROOF INSTEAD OF GABLE ROOFS.
  
 43- SHEET S-1.4: A) SPECIFY CONNECTORS
 FOR ROOF TRUSSES.
 B) WOOD EXTERIOR STAIRS OR CONCRETE
 STAIRS. ARCHITECTURAL DWGS AND
 STRUCTURAL DRAWINGS TO MATCH AND PROVIDE
 COMPLETE STRUCTURAL DETAILS/SPECS.
 C) FOOTING F20.12 FOR STAIRS IS NOT IN
 THE FOOTING SCHEDULE. PROVIDE INFO.
 D) GROUND FLOOR NEEDS TO BE ACCESSIBLE
 TO COMPLY WITH CHAPTER 11 FBC 2004.
  
 44- SHEET S-1.5: MISSING COLUMN SCHEDULE
 AND TOP AND BOTTOM COLUMN CONNECTIONS
 FOR INTERIOR COLUMNS. THIS COMMENT
 APPLIES TO ALL BUILDING TYPES.
  
 45- SHEET S-1.6: A) LEASING OFFICE AND
 GOUND UNITS NEED TO BE ACCESSIBLE TO
 COMPLY WITH CHAPTER 11 FBC 2004 AND FAIR
 HOUSING ACT. FOUNDATION PLAN NEED TO BE
 REVISED ACCORDINGLY TO SHOW
 ACCESSIBILITY.
 B) STAIR #2 TO MATCH ARCHITECTURAL
 DWGS. CHECK LOCATION OF FIRST RISER
 GOING DOWN FROM 2ND FLOOR.
 C) PROVIDE COMPLETE 2ND FLOOR FRAMING
 PLAN. SHOW TRUSS GIRDERS AROUND STAIR
 OPENINGS.
 D) SPECIFY ALL LIVE AND DEAD LOADS.
  
 46- SHEET S-2.1: A) TRUSS TIE DOWN
 SCHEDULE. REVISE SPECS FOR CONNECTORS C
 AND G TO MATCH MANUFACTURER'S PUBLISHED
 VALUES. EG CONNECTOR TYPE, EMBEDMENT AND
 UPLIFT VALUES. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS TO SHOW
 WHY SPECS WERE CHANGED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: THIS COMMENT APPLIES TO ALL
 STRUCTURAL DRAWINGS WITH THE TRUSS TIE
 DOWN SCHEDULE. REVISE ALL OF THEM.
 B) REVISE DESIGN LOAD SCHEDULE FOR
 LEASING OFFICE. SEE TABLE 1607.1 FBC
 2004. MAKE SURE CLEAR SPECIFICATIONS ARE
 DONE FOR MULTIFAMILY UNITS AND FOR
 LEASING OFFICE AND COMMUNITY BUILDING.
  
 47- SHEET S-2.6: A) REVISE TIE BEAM
 ELEVATION FOR LEASING OFFICE AREA.
 ARCHITECTURAL DRAWINGS AND STRUCTURAL
 DRAWINGS TO MATCH.
 B) PROVIDE TIE BEAM ELEVATION FOR STAIR
 #2. CHECK ARCHITECTURAL DRAWINGS.
  
 48- SHEETS S-4.1 THRU S-4.4: DRAWINGS
 ARE NOT LEGIBLE. ELEVATION ARE TOO
 LIGHT. SAME COMMENT APPLIES TO SHEETS
 S-5.6, S-5.8, S-6.5, S-6.7 AND S-6.10.
  
 49- LEASING OFFICE: SPECIFY FIRE RATING
 ON INTERIOR DOOR AND WINDOWS AND PROVIDE
 PRODUCT APPROVALS AS REQUIRED.
  
 50- BEFORE APPLYING FOR BUILDING PERMITS
 COORDINATE WITH HAROLD PISKURA,
 INSPECTION SERVICES MANAGER, IF SPECIAL
 INSPECTOR WILL BE REQUIRED/DESIRED TO
 MAKE SURE THERE IS NOT CONFLICT BETWEEN
 INSPECTIONS AND PROGRESS OF WORK. IF
 SPECIAL INSPECTOR IS REQUESTED, THEN 3
 COMPLETE SETS OF CONSTRUCTION DOCUMENTS
 ARE REQUIRED TO BE SUBMITTED.
  
 51- PROVIDE COMPLETE SET OF TRUSS
 DRAWINGS FOR REVIEW. TRUSS PACKAGE TO BE
 REVIEWED AND APPROVED BY ENGINEER OF
 RECORD PRIOR TO SUBMITTAL.
  
 52- ALL APPARTMENT UNITS WITH WINDOW
 TYPE B NEED TO SPECIFY WINDOW SILL TO
 VERIFY COMPLIANCE WITH SAFETY GLASS.
  
 53- TYPE VI IS AN SPRINKLERED BUILDING.
 NEED SEPARATE PERMIT APPLICATION FOR
 SPRINKLER SYSTEM. BUT, NEED TO PROVIDE
 SPRINKLER HEAD LAYOUT FOR REVIEW ALONG
 WITH PERMIT APPLICATION FOR THIS BLDG.
  
 54- ALL PRODUCT APPROVALS NED TO BE
 REVIEWED AND APPROVED IN WRITTING BY
 DESIGNER OF RECORD AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
 TYPICALLY THIS IS DONE USING THE
 STANDARD REVIEW AND APPROVE STAMP.
  
 55- PROVIDE ALL FLORIDA OR LOCAL PRODUCT
 APPROVALS AS REQUIRED BY RULE 9B-72. GO
 TO WWW.FLORIDABUILDING.ORG TO REVIEW AND
 DOWNLOAD ALL PRODUCT APPROVALS. PROVIDE
 FLORIDA COVER PAGE AND SPECIFIC DADE
 COUNTY NOA OR DRAWINGS THAT WERE
 SUBMITTED TO OBTAIN THE FLORIDA PRODUCT
 APPROVAL.
 ***NOTE: PROVIDE ONLY PRODUCT APPROVALS
 FOR PRODUCT TO BE USED. EG: THERE ARE
 NOT SLIDING GLASS DOORS IN THESE PLANS.
 A) FLAT ROOF SYSTEM. CLEARLY IDENTIFY
 SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH
 GENERAL LIMITATION #7 OR #9. SEE GENERAL
 LIMITATION ON LAST PAGE OF NOA. ALSO,
 SEE ATTACHED COPY OF CITY POLICY FOR
 ROOFING PERMITS.
 NOTE: GENERAL LIMITATION #7 REQUIRES
 CALCULATIONS FOR PERIMETER AND CORNER
 AREAS NAIL ENHANCEMENT. PROVIDE THEM.
 B) SHINGLES. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE. GO TO WEBSITE
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD IT.
 ALSO, REVISE ARCHITECTURAL DETAIL TO
 MATCH PRODUCT APPROVAL.
 C) 2HR FIRE RATED CONCRETE BLOCK.
 D) STRUCTURAL MULLIONS SPECIFIED FOR
 WINDOWS AND DOORS. SEE PLANS. AND
 CLEARLY IDENTIFY SPECIFIC ANCHORS TO BE
 USED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
 E) STORM SHUTTERS WITH KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE. (WHY SUBMITTING 2
 DIFFERENT MANUFACTURER'S).
 F) ALL STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS. SEE TRUSS ANCHOR SCHEDULE AND
 ALL SECTIONS AND DETAILS.
 G) TYPE OF SIDING SPECIFIED ON PLANS.
 H) APARTMENT UNITS ENTRY DOORS.
 I) LEASING OFFICE ENTRY DOORS.
 J) LEASING OFFICE STAIR #2 EXT. DOOR.
 K) COMMUNITY ROOM ENTRY DOORS.
 L) COMMUNITY ROOM FIXED WINDOWS.
 M) ALL OTHER FIXED WINDOWS.
 N) FRENCH DOORS AT LEASING BUILDING.
 O) FRENCH DOORS ON BALCONIES AT 2ND
 STORY APARTMENT BUILDINGS.
 P) SINGLE HUNG WINDOWS.
 Q) ROOF RIDGE VENT. AND REVISE
 ARCHITECTURAL DETAIL TO MATCH PRODUCT
 APPROVAL).
  
 NOTES: * PROVIDE ONLY PRODUCT APPROVALS
 THAT APPLY TO EACH BUILDING WHEN
 APPLYING FOR BUILDING PERMIT.
 ** CLEARLY IDENTIFY PRODUCT APPROVALS.
 EG: LEASING OFFICE DOOR. TO EXPEDITE
 REVIEW PROCESS.
 *** COORDINATE SHUTTERS INSTALLATION
 WITH ITEM #56. SOME WINDOW/DOOR PRODUCT
 APPROVALS WILL REQUIRE IMPACT GLASS.
  
 56- INSTALLATION OF STORM PANELS FOR
 LARGE BUILDINGS NEED THE APPROVAL IN
 WRITTING BY THE BUILDING OFFICIAL. SEE
 ITEMS 13 AND 14 OF ATTACHED COPY OF CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION.
  
 57- PROVIDE SPECIFICATIONS FOR DOOR
 HARDWARE AT ACCESSIBLE UNITS, LEASING
 OFFICE AND COMMUNITY ROOM.
  
 58- PROVIDE COMPLETE DETAILS AND SPECS
 SHOWING COMPLIANCE WITH SEC. 1207 FBC
 2004 FOR SOUND TRANSMISSION.
  
 59- PROVIDE COMPLETE DETAILS/SPECS AND
 STRUCTURAL DETAILS FOR LEASING OFFICE
 ELEVATOR.
  
 60- PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712