| Date |
Text |
| 2006-05-18 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) CONSTRUCTION DOCUMENTS SHALL INDICATE |
| | THE WIND DESIGN DATA AS REQUIRED IN |
| | 1603.1.4 FBC INCLUDING EXTERIOR |
| | COMPONENT AND CLADDING PRESSURES FOR |
| | WINDOWS, DOORS, ROOFING, ETC. ALSO |
| | PROVIDE FLOOR AND ROOF LOADS |
| | |
| | 2) DEMO NOTES ON PAGE D1 STATE ROOF TO |
| | REMAIN BUT S1 SHOWS NEW WOOD TRUSSES |
| | PLEASE CLARIFY |
| | |
| | 3) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | NOTE: PROVIDE PRODUCT APPROVALS FOR |
| | ROOFING TILES, FLAT ROOF AND WOOD |
| | CONNECTORS. FL APPROVAL SHEETS FROM |
| | SIMPSON WEB SITE IS ADEQUATE SEE |
| | ENCLOSED SAMPLE |
| | |
| | 4) THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 5) CBC LICENCE DOES NOT ALLOW CONTRACTOR |
| | TO ACT AS ROOFER OR INSTALL ROOFING |
| | OTHER THAN WOOD SHAKES/SHINGLES OR |
| | ASPHALT/FIBERGLASS SHINGLES ON A NEW |
| | BUILDING OF HIS/HER OWN CONSTRUCTION PER |
| | 489.114 (3)(B),(G) FS |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 6) PROVIDE DETAILS OF STRUCTURAL FRAMING |
| | AT DOOR AND WINDOW OPENINGS SHOWING WOOD |
| | CONNECTOR TYPES THAT WILL BE USED IN |
| | ORDER TO TRANSFER THE PRESSURES FROM NEW |
| | COMPONENTS TO THE STRUCTURE |
| | |
| | 7) POWDER ROOM DR TO MEET ACCESSABILITY |
| | REQUIREMENTS PER R322.1.1 FBC |
| | |
| | 8) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION |
| | |
| | 9) ENERGY CALC'S SHOW R30 CEILING |
| | INSULATION, DETAIL 3 ON A4 HAS R19 |
| | PLEASE CLARIFY |
| | |
| | 10) ENERGY CALC'S NOT SIGNED AND DATED |
| | BY OWNER/AGENT |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | BLDG PLAN REVIEW |