| Date |
Text |
| 2006-04-26 00:00:00 | 1) ALL CONSTRUCTION DOCUMENTS BEING |
| | FILED FOR PUBLIC RECORD SHALL BE OF |
| | SUFFICIENT CLARITY. SEE THE SHEETS |
| | D-1/A-1/A-2 AND A-3. THERE IS NO |
| | INFORMATION ON THE SEAL. |
| | |
| | (2) 481.221SEALS;DISPLAY OF |
| | CERTIFICATE NUMBER.-- |
| | (2)EACH REGISTERED ARCHITECT SHALL |
| | OBTAIN ONE SEAL IN A FORM APPROVED BY |
| | RULE OF THE BOARD AND MAY, IN ADDITION, |
| | REGISTER HER OR HIS SEAL ELECTRONICALLY |
| | IN ACCORDANCE WITH SS. 668.001-668.006. |
| | ALL FINAL CONSTRUCTION DOCUMENTS AND |
| | INSTRUMENTS OF SERVICE WHICH INCLUDE |
| | DRAWINGS, PLANS, SPECIFICATIONS, OR |
| | REPORTS PREPARED OR ISSUED BY THE |
| | REGISTERED ARCHITECT AND BEING FILED FOR |
| | PUBLIC RECORD SHALL BEAR THE SIGNATURE |
| | AND SEAL OF THE REGISTERED ARCHITECT WHO |
| | PREPARED OR APPROVED THE DOCUMENT AND |
| | THE DATE ON WHICH THEY WERE SEALED. THE |
| | SIGNATURE, DATE, AND SEAL SHALL BE |
| | EVIDENCE OF THE AUTHENTICITY OF THAT TO |
| | WHICH THEY ARE AFFIXED. |
| | (8)FINAL CONSTRUCTION DOCUMENTS OR |
| | INSTRUMENTS OF SERVICE WHICH INCLUDE |
| | PLANS, DRAWINGS, SPECIFICATIONS, OR |
| | OTHER ARCHITECTURAL DOCUMENTS PREPARED |
| | BY A REGISTERED ARCHITECT AS PART OF HER |
| | OR HIS ARCHITECTURAL PRACTICE SHALL BE |
| | OF A SUFFICIENTLY HIGH STANDARD TO |
| | CLEARLY AND ACCURATELY INDICATE OR |
| | ILLUSTRATE ALL ESSENTIAL PARTS OF THE |
| | WORK TO WHICH THEY REFER. |
| | |
| | 3) DOOR #116 ON SHEET A-1 SHOWS A LEFT |
| | SWING HOWEVER, ON SHEETS E2.1 AND E3.1 |
| | THE SAME DOOR SHOWS A RIGHT SWING. |
| | PLEASE SHOW MATCHING FLOOR LAY-OUT ON |
| | ALL FLOOR PLANS. 11-4.13.6 MANEUVERING |
| | CLEARANCES AT DOORS. MINIMUM MANEUVERING |
| | CLEARANCES AT DOORS THAT ARE NOT |
| | AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| | SHOWN IN FIGURE 11-25 . THE FLOOR OR |
| | GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE LEVEL AND CLEAR. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |