| Date |
Text |
| 2006-05-16 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) PAGE 2 OF PERMIT APPLICATION IS |
| | MISSING PLEASE RE SUBMIT |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION |
| | |
| | 3) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* |
| | |
| | 4) ON THE ENERGY CALC'S UNDER ITEM 9 |
| | WALL TYPE SHOULD INCLUDE WOOD FRAME WITH |
| | R19 |
| | |
| | 5) SOIL REPORT ADDRESSES THE SOIL FOR |
| | SHALLOW FOUNDATIONS AS PROBLEMATIC HAVE |
| | YOUR ENGINEER VERIFY THAT FOUNDATION IS |
| | ADEQUATE |
| | |
| | 6) DETAIL CONNECTION OF EXISTING WALLS, |
| | TIE BEAMS AND FOUNDATIONS TO NEW WALLS, |
| | TIE BEAMS AND FOUNDATIONS |
| | |
| | 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION |
| | |
| | 8) PLEASE CHECK ALL CONNECTORS AS MANY |
| | ARE NOT AVAILABLE AS LISTED ON DRAWING |
| | |
| | 9) SECTION A4-A IS THROUGH EXTERIOR WALL |
| | NOT STAIR OPENING AS SHOWN ON FLOOR PLAN |
| | |
| | 10) PROVIDE ATTIC ACCESS AS REQUIRED PER |
| | R807.1 FBC |
| | |
| | 11) SEE STAIR LAYOUT ON A2. THIS LAYOUT |
| | WILL NOT WORK WITH FLOOR JOIST |
| | CONFIGURATION ON A5. TOP 2 RISERS PASS |
| | THROUGH DOUBLE GIRDER TRUSS, WINDER AT |
| | BOTTOM WILL NOT ALLOW MIN HEAD CLEARANCE |
| | AT FLOOR OPENING |
| | |
| | 12) THE FOLLOWING IS A LIST OF PROBLEMS |
| | WITH THE PRODUCT APPROVALS |
| | A) PRECAST LINTELS- CORRECT FL COVER |
| | WRONG NOA THIS COVERS 4,6 AND 12 INCH |
| | LINTELS NOT 8" |
| | B) PGT WINDOWS- OUT DATED FL COVER |
| | SHOULD BE FL239-R4 AND EXPIRED NOA |
| | C) GARAGE DOOR- NON EXISTENT FL COVER |
| | NOW UNDER FL4913 AND DRAWING IS UPDATED |
| | TO REVISION 9 YOU HAVE SUBMITTED |
| | REVISION 5 |
| | D) ROOF SHINGLES- NOA HAS EXPIRED IF |
| | USING NEW MIAMI-DADE NOA IT IS NOT THE |
| | DRAWING PROVIDED UNDER THE STATE PRODUCT |
| | APPROVAL BUT IT IS COVERED UNDER A LOCAL |
| | PRODUCT APPROVAL |
| | E) STORM PANELS- FL COVER IS CORRECT |
| | BUT NO DRAWINGS WERE SUBMITTED PLEASE |
| | SUBMIT WITH CONNECTION METHOD,TYPE OF |
| | ANCHOR, ETC. MARKED/CIRCLED THAT WILL BE |
| | USED. |
| | F) PROVIDE LIST OF STRAPS/CONNECTORS |
| | THAT WILL BE USED AND THEIR FL#'S |
| | |
| | 13) THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | BLDG PLAN REVIEW |