2006-05-16 00:00:00 
  
 DENIED
  
 1) PAGE 2 OF PERMIT APPLICATION IS
 MISSING PLEASE RE SUBMIT
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 3) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 4) ON THE ENERGY CALC'S UNDER ITEM 9
 WALL TYPE SHOULD INCLUDE WOOD FRAME WITH
 R19
  
 5) SOIL REPORT ADDRESSES THE SOIL FOR
 SHALLOW FOUNDATIONS AS PROBLEMATIC HAVE
 YOUR ENGINEER VERIFY THAT FOUNDATION IS
 ADEQUATE
  
 6) DETAIL CONNECTION OF EXISTING WALLS,
 TIE BEAMS AND FOUNDATIONS TO NEW WALLS,
 TIE BEAMS AND FOUNDATIONS
  
 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 8) PLEASE CHECK ALL CONNECTORS AS MANY
 ARE NOT AVAILABLE AS LISTED ON DRAWING
  
 9) SECTION A4-A IS THROUGH EXTERIOR WALL
 NOT STAIR OPENING AS SHOWN ON FLOOR PLAN
  
 10) PROVIDE ATTIC ACCESS AS REQUIRED PER
 R807.1 FBC
  
 11) SEE STAIR LAYOUT ON A2. THIS LAYOUT
 WILL NOT WORK WITH FLOOR JOIST
 CONFIGURATION ON A5. TOP 2 RISERS PASS
 THROUGH DOUBLE GIRDER TRUSS, WINDER AT
 BOTTOM WILL NOT ALLOW MIN HEAD CLEARANCE
 AT FLOOR OPENING
  
 12) THE FOLLOWING IS A LIST OF PROBLEMS
 WITH THE PRODUCT APPROVALS
 A) PRECAST LINTELS- CORRECT FL COVER
 WRONG NOA THIS COVERS 4,6 AND 12 INCH
 LINTELS NOT 8"
 B) PGT WINDOWS- OUT DATED FL COVER
 SHOULD BE FL239-R4 AND EXPIRED NOA
 C) GARAGE DOOR- NON EXISTENT FL COVER
 NOW UNDER FL4913 AND DRAWING IS UPDATED
 TO REVISION 9 YOU HAVE SUBMITTED
 REVISION 5
 D) ROOF SHINGLES- NOA HAS EXPIRED IF
 USING NEW MIAMI-DADE NOA IT IS NOT THE
 DRAWING PROVIDED UNDER THE STATE PRODUCT
 APPROVAL BUT IT IS COVERED UNDER A LOCAL
 PRODUCT APPROVAL
 E) STORM PANELS- FL COVER IS CORRECT
 BUT NO DRAWINGS WERE SUBMITTED PLEASE
 SUBMIT WITH CONNECTION METHOD,TYPE OF
 ANCHOR, ETC. MARKED/CIRCLED THAT WILL BE
 USED.
 F) PROVIDE LIST OF STRAPS/CONNECTORS
 THAT WILL BE USED AND THEIR FL#'S
  
 13) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  