Plan Review Notes
Plan Review Notes For Permit 06040145
Permit Number 06040145
Review Stop E
Sequence Number 4
Notes
Date Text
2006-08-06 00:00:00****** UNSAT 3RD REVIEW ********
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW COMMENTS AS PLANS DO NOT MEET
 CODE COMPLAINCE.
  
  
 1) NOTE: **IMPORTANT**
 PLEASE REMOVE ALL
 OLD/VOIDED SHEETS FROM EXISTING SETS AND
 INSERT ONLY NEW REVISED SHEETS INTO "TWO
 COMPLETE SETS" FOR REVIEW AND STAMPING.
 PLEASE SEE SEPARATE SHEETS ARE IN
 MULTIPLE LOCATIONS ON PACKAGE SUBMITTED.
 SETS SHALL BE MADE UP INTO SETS BY THE
 RESPONSIBLE PARTY TO AVOID DELAYS AND
 EXPEDITE THE REVIEW PROCESS.
 106.1 ADMIN SECT FBC
  
 2) NOTE: NO, PLEASE SEE THIS IS STILL
 NOT DONE. PLEASE SEE MECHANICAL PLANS
 WHICH SHOW DIFFERENT SIZE AHU/HEAT ETC.
 PLEASE ALSO SEE ONLY ONE SET CONTAINS A
 "M" SHEETS. SEE MECH REVIEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRLEATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS AS THERE ARE
 MORE THAN ONE HEAT KW SIZE SHOWN. PLEASE
 ALSO SEE MULTIPLE SETS OF "M" SHEETS AE
 SUBMITTED AND SEEING THAT NOW REVISIONS
 ARE SHOWN WITH CLOUDS/TRIANGLESS OR
 REVISED DATES, IT IS UNCLEAR WHICH "M"
 SHEETS APPLY. PLEASE SEE BOTH CONTAIN A
 DATE OF MARCH 13??????
 215.5, 106.1.2
  
 3) NOTE: NO, SAME COMMENT NOT ADDRESSED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 424.3B FOR MIN OCP
 TO BE SIZED FOR AHU. (125% MIN). PLEASE
 ALSO ADJUST CONDUCTOR SIZES PER 310.16.
 FOR BOTH AHU'S.
  
 4) NOTE:NO, NOT DONE, AS REQUESTED
 SHOW ALL MEETING CURRENT CODE OR NEW
 WHICH WILL MEET CURRENT CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE ENTIRE EXISTING
 DWELLING AS SD'S ARE REQUIRED IN ALL
 EXISTING BEDRMS INSIDE AND OUTSIDE ROOMS
 AND ONLY PART OF THE EXISTING DWELLING
 IS SHOWN.
 PLEASE KNOW, ALL NEW SD'S ARE REQUIRD TO
 BE INSTALLED PER CURRENT NFPA-72
 11.5.1.1,11.8.3.
 R313, 2004 FBC.
  
 5) NOTE: NO, SAME WALL REDLINED ON
 PREVIOUS PLANS STILL DOES NOT CONTAIN
 ELECTRICAL RECEPT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING RECEPT(S) PER
 210.52.
  
 6) NOTE: NO, PLEASE SEE DISCONNECT IS
 STILL NOT SHOWN . NOTE MENTIONS THIS IS
 "CEILING HUNG" THIS WOULD PALCE UNIT IN
 THE ROOM?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DISCONNECT
 FOR AHU IN ATTIC. 440.11.
  
 7) NOTE:NO, DSAME COMMENT. PLEASE SEE
 THIS WAS NOTED ON THE FIRST REVIEW TO
 CORRELATE ALL LOADS, AND ITEMS ON PANEL
 SCHEDULES. THIS IS STILL NOT DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE NUMEROUS
 ITEMS ON PANEL SCHEDULE AND THE LOAD
 CALCULATIONS WHICH DO NOT CORRELATE.
 PLEASE SEE MANY ITEMS WHICH ARE SHOWN IN
 LOAD CALCULATIONS, ARE NOT ON PANEL
 SCHEDULE.IE: RANGE, COOKTOP, WHIRLPOOL,
 WATER HEATER, ETC ETC ETC
 215.5, 106.1.2, 408.4, 220.31B
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: NO, SAME NOTE: STILL SHOWS #8
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE ONE OF THE NEW BATH
 CIRCUITS WITH #8 AWG??
 210.11C3 (20A #12).
  
 12) NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS AND REQUIRED METHOD TO BE
 SHOWN.
 215.5,106.1.2
  
 13) NOTE:PLEASE A 4X FEE FOR PLAN
 REVIEW HAS NOW BEEN ASSESSED TO THE
 DEISGN PROFESSIONAL. PLEASE ALSO KNOW,
 AS PLANS FOR THIS PROJECT AND OTHER
 PROJECTS HAVE BEEN RETIANED BY THIS
 OFFICE FOR REPEAT CODE COMPLIANT
 COMMENTS THESE SHALL BE FORWARDED TO THE
 STATE OF FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS AND THE STATE'S LEGAL COUNSEL
 TO THE BOARD.
 PLEASE KNOW THE FEE OF $1,539.93 IS NOW
 DUE FROM THE DESIGN PROFESSIONAL BEFORE
 PLANS CAN BE RESUBMITTED.
 ** THIS IS NOT THE RESPONSIBLITY OF THE
 OWNER OR CONTRACTOR.
 A 3RD REVIEWED SET IS ALSO NOW RETAINED
 AND WILL BE PLACED WITH OTHER PLANS.
  
 ** PLEASE SEE FS 471.025(3) WHICH
 STATE'S:
 "NO LICENSEE SHALL AFFIX OR PERMIT TO BE
 AFFIXED HIS OR HER SEAL, NAME, OR
 DIGITAL SIGNATURE TO ANY PLAN,
 SPECIFICATION, DRAWING, FINAL BID
 DOCUMENT, OR OTHER DOCUMENT THAT DEPICTS
 WORK WHICH HE OR SHE IS NOT LICENSED TO
 PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN."
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
 PLEASE KNOW, THIS IS ONLY NOTICE GIVEN
 AT THIS TIME.
 ** PLEASE KNOW, TWO "E" SHEETS ARE BEING
 RETAINED FOR FILE.
  
 ** NEW NOTE **
  
 14) NOTE: PLEASE SEE PREVIOUS LOAD CALCS
 CONTIANED A GARAGE DOOR OPENER.? IF THIS
 LOAD IS AT LOCATION OF DWELLING, THEN
 THIS SHOULD BE INCLUDED ON PANEL
 SCHEDULE AND LOAD CALCS.
 220
  
 15) NOTE: PLEASE SEE PLANS CONTAIN A
 MAIN DISCONNECT OUTSIDE AND ONLY A PANEL
 IS BEING SHOWN ON RISER.
 PLEASE CORRELATE. IF THERE IS NOW A NEW
 MAIN DISCONNECT, PLEASE INLCUDE ITS AIC
 RATING, CONDUCTORS, SIZE ETC.
 UNABLE TO VERIFY AT THIS TIME.
 240.4,310.16,,250.24B,250.122, 215.5
 ETC
  
  
 ** PLEASE KNOW, THE NOTES ABOVE HAVE NO
 WAY SPECIFICALLY NOTED EVERY ITEM NOT
 CORRECT, HOWEVER ALL CODES HAVE BEEN
 GIVEN FOR ITEMS WHICH ARE NOT CORRECT ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  