2006-08-10 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-28-06 NOTE
 #2. MANUAL J CALCULATIONS ARE CALLING
 FOR 8,608 TOTAL SENSIBLE BTU'S,
 MECHANICAL PLANS ARE CALLING FOR 16,400
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL
 FOR 20% MORE THAN THE MANUAL J CAL'S,
 PER 2004 FBC 13-607.1.ABC.1.1, PLEASE
 CORRECT. (THE A/C SYSTEM ON THE
 MECHANICAL PLANS IS TO LARGE).
  
 2) ONLY ONE MECHANICAL PLAN WAS
 SUBMITTED, TWO COPYS NEED TO BE
 SUBMITTED.
  
 3) SHOW ON MECHANICAL PLANS EQUIPMENT
 LIST AIR HANDLER UNIT'S TOTAL CFM'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.