| Notes |
| Date |
Text |
| 2006-08-10 00:00:00 | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 6-28-06 NOTE | | | #2. MANUAL J CALCULATIONS ARE CALLING | | | FOR 8,608 TOTAL SENSIBLE BTU'S, | | | MECHANICAL PLANS ARE CALLING FOR 16,400 | | | SENSIBLE BTU'S, THE PLANS CAN ONLY CALL | | | FOR 20% MORE THAN THE MANUAL J CAL'S, | | | PER 2004 FBC 13-607.1.ABC.1.1, PLEASE | | | CORRECT. (THE A/C SYSTEM ON THE | | | MECHANICAL PLANS IS TO LARGE). | | | | | | 2) ONLY ONE MECHANICAL PLAN WAS | | | SUBMITTED, TWO COPYS NEED TO BE | | | SUBMITTED. | | | | | | 3) SHOW ON MECHANICAL PLANS EQUIPMENT | | | LIST AIR HANDLER UNIT'S TOTAL CFM'S. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|