2006-06-28 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 4-20-06
 NOTE #1, PLEASE SUBMIT TWO COPYS OF THE
 ENERGY CALCULATIONS.
  
 2) MANUAL J CALCULATIONS ARE CALLING FOR
 8,608 TOTAL SENSIBLE BTU'S, MECHANICAL
 PLANS ARE CALLING FOR 16,400 SENSIBLE
 BTU'S, THE PLANS CAN ONLY CALL FOR 20%
 MORE THAN THE MANUAL J CAL'S, PER 2004
 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.