| Plan Review Notes For Permit 06040145 |
| Permit Number |
06040145 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-28 00:00:00 | *** DENIED *** | | | 1) AS REQUESTED IN LAST REVIEW 4-20-06 | | | NOTE #1, PLEASE SUBMIT TWO COPYS OF THE | | | ENERGY CALCULATIONS. | | | | | | 2) MANUAL J CALCULATIONS ARE CALLING FOR | | | 8,608 TOTAL SENSIBLE BTU'S, MECHANICAL | | | PLANS ARE CALLING FOR 16,400 SENSIBLE | | | BTU'S, THE PLANS CAN ONLY CALL FOR 20% | | | MORE THAN THE MANUAL J CAL'S, PER 2004 | | | FBC 13-607.1.ABC.1.1, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|