Plan Review Notes
Plan Review Notes For Permit 06040145
Permit Number 06040145
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-27 00:00:00****** UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW COMMENTS AS PLANS DO NOT MEET
 CODE COMPLAINCE.
  
  
 1) NOTE: **IMPORTANT** PLEASE REMOVE ALL
 OLD/VOIDED SHEETS FROM EXISTING SETS AND
 INSERT ONLY NEW REVISED SHEETS INTO "TWO
 COMPLETE SETS" FOR REVIEW AND STAMPING.
 PLEASE SEE SEPARATE SHEETS ARE IN
 MULTIPLE LOCATIONS ON PACKAGE SUBMITTED.
 SETS SHALL BE MADE UP INTO SETS BY THE
 RESPONSIBLE PARTY TO AVOID DELAYS AND
 EXPEDITE THE REVIEW PROCESS.
 106.1 ADMIN SECT FBC
  
 2) NOTE: PLEASE CORRLEATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS AS THERE ARE
 MORE THAN ONE HEAT KW SIZE SHOWN. PLEASE
 ALSO SEE MULTIPLE SETS OF "M" SHEETS AE
 SUBMITTED AND SEEING THAT NOW REVISIONS
 ARE SHOWN WITH CLOUDS/TRIANGLESS OR
 REVISED DATES, IT IS UNCLEAR WHICH "M"
 SHEETS APPLY. PLEASE SEE BOTH CONTAIN A
 DATE OF MARCH 13??????
 215.5, 106.1.2
  
 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 TO BE SIZED FOR AHU. (125% MIN). PLEASE
 ALSO ADJUST CONDUCTOR SIZES PER 310.16.
 FOR BOTH AHU'S.
  
 4) NOTE: PLEASE SHOW THE ENTIRE EXISTING
 DWELLING AS SD'S ARE REQUIRED IN ALL
 EXISTING BEDRMS INSIDE AND OUTSIDE ROOMS
 AND ONLY PART OF THE EXISTING DWELLING
 IS SHOWN.
 PLEASE KNOW, ALL NEW SD'S ARE REQUIRD TO
 BE INSTALLED PER CURRENT NFPA-72
 11.5.1.1,11.8.3.
 R313, 2004 FBC.
  
 5) NOTE: PLEASE SEE MISSING RECEPT PER
 210.52.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR AHU IN ATTCI. 440.11.
  
 7) NOTE: PLEASE SEE THERE ARE NUMEROUS
 ITEMS ON PANEL SCHEDULE AND THE LOAD
 CALCULATIONS WHICH DO NOT CORRELATE.
 PLEASE SEE MANY ITEMS WHICH ARE SHOWN IN
 LOAD CALCULATIONS, ARE NOT ON PANEL
 SCHEDULE.IE: RANGE, COOKTOP, WHIRLPOOL,
 WATER HEATER, ETC ETC ETC
 215.5, 106.1.2, 408.4, 220.31B
  
 8) NOTE: PLEASE SEE MANY ITEMS LISTED IN
 LOAD CALCS ARE MENTIONED IN"PLURAL"??
 PLEASE VERIFY AS SOME ARE ONLY SHOWN AS
 ONE/SINGULAR ON PANEL SCHEDULE.
 IE: WASHERS, WATER HEATERS,DISHAWSHERS,
 ETC ETC
 215.5,106.1.2, 408.4
  
 9) NOTE: PLEASE SEE 310.16, 240.4 FOR
 MIN OCP AND AWG REQUIRED FOR DRYER.
 215.5, 106.1.2
  
 10) NOTE: PLEASE SEE 20A LIGHTING
 CIRCUIT BEING SHOWN IN LOAD CALCS WHICH
 INDICATE 3KW LOAD????
 PLEASE SEE MAX KVA ON THE 20A CIR IS
 1920VA.
 240.4, ETC
  
 11) NOTE: PLEASE SEE ONE OF THE NEW BATH
 CIRCUITS WITH #8 AWG??
 210.11C3 (20A #12).
  
 12) NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS AND REQUIRED METHOD TO BE
 SHOWN.
 215.5,106.1.2
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
 PLEASE KNOW, THIS IS ONLY NOTICE GIVEN
 AT THIS TIME.
 ** PLEASE KNOW, TWO "E" SHEETS ARE BEING
 RETAINED FOR FILE.
  
 ** PLEASE KNOW, THE NOTES ABOVE HAVE NO
 WAY SPECIFICALLY NOTED EVERY ITEM NOT
 CORRECT, HOWEVER ALL CODES HAVE BEEN
 GIVEN FOR ITEMS WHICH ARE NOT CORRECT ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  