| 2006-06-27 00:00:00 | ****** UNSAT 2ND REVIEW ******** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED ALONG |
| | WITH NEW COMMENTS AS PLANS DO NOT MEET |
| | CODE COMPLAINCE. |
| | |
| | |
| | 1) NOTE: **IMPORTANT** PLEASE REMOVE ALL |
| | OLD/VOIDED SHEETS FROM EXISTING SETS AND |
| | INSERT ONLY NEW REVISED SHEETS INTO "TWO |
| | COMPLETE SETS" FOR REVIEW AND STAMPING. |
| | PLEASE SEE SEPARATE SHEETS ARE IN |
| | MULTIPLE LOCATIONS ON PACKAGE SUBMITTED. |
| | SETS SHALL BE MADE UP INTO SETS BY THE |
| | RESPONSIBLE PARTY TO AVOID DELAYS AND |
| | EXPEDITE THE REVIEW PROCESS. |
| | 106.1 ADMIN SECT FBC |
| | |
| | 2) NOTE: PLEASE CORRLEATE MECHANICAL |
| | PLANS WITH ELECTRICAL PLANS AS THERE ARE |
| | MORE THAN ONE HEAT KW SIZE SHOWN. PLEASE |
| | ALSO SEE MULTIPLE SETS OF "M" SHEETS AE |
| | SUBMITTED AND SEEING THAT NOW REVISIONS |
| | ARE SHOWN WITH CLOUDS/TRIANGLESS OR |
| | REVISED DATES, IT IS UNCLEAR WHICH "M" |
| | SHEETS APPLY. PLEASE SEE BOTH CONTAIN A |
| | DATE OF MARCH 13?????? |
| | 215.5, 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | TO BE SIZED FOR AHU. (125% MIN). PLEASE |
| | ALSO ADJUST CONDUCTOR SIZES PER 310.16. |
| | FOR BOTH AHU'S. |
| | |
| | 4) NOTE: PLEASE SHOW THE ENTIRE EXISTING |
| | DWELLING AS SD'S ARE REQUIRED IN ALL |
| | EXISTING BEDRMS INSIDE AND OUTSIDE ROOMS |
| | AND ONLY PART OF THE EXISTING DWELLING |
| | IS SHOWN. |
| | PLEASE KNOW, ALL NEW SD'S ARE REQUIRD TO |
| | BE INSTALLED PER CURRENT NFPA-72 |
| | 11.5.1.1,11.8.3. |
| | R313, 2004 FBC. |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.52. |
| | |
| | 6) NOTE: PLEASE SEE MISSING DISCONNECT |
| | FOR AHU IN ATTCI. 440.11. |
| | |
| | 7) NOTE: PLEASE SEE THERE ARE NUMEROUS |
| | ITEMS ON PANEL SCHEDULE AND THE LOAD |
| | CALCULATIONS WHICH DO NOT CORRELATE. |
| | PLEASE SEE MANY ITEMS WHICH ARE SHOWN IN |
| | LOAD CALCULATIONS, ARE NOT ON PANEL |
| | SCHEDULE.IE: RANGE, COOKTOP, WHIRLPOOL, |
| | WATER HEATER, ETC ETC ETC |
| | 215.5, 106.1.2, 408.4, 220.31B |
| | |
| | 8) NOTE: PLEASE SEE MANY ITEMS LISTED IN |
| | LOAD CALCS ARE MENTIONED IN"PLURAL"?? |
| | PLEASE VERIFY AS SOME ARE ONLY SHOWN AS |
| | ONE/SINGULAR ON PANEL SCHEDULE. |
| | IE: WASHERS, WATER HEATERS,DISHAWSHERS, |
| | ETC ETC |
| | 215.5,106.1.2, 408.4 |
| | |
| | 9) NOTE: PLEASE SEE 310.16, 240.4 FOR |
| | MIN OCP AND AWG REQUIRED FOR DRYER. |
| | 215.5, 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE 20A LIGHTING |
| | CIRCUIT BEING SHOWN IN LOAD CALCS WHICH |
| | INDICATE 3KW LOAD???? |
| | PLEASE SEE MAX KVA ON THE 20A CIR IS |
| | 1920VA. |
| | 240.4, ETC |
| | |
| | 11) NOTE: PLEASE SEE ONE OF THE NEW BATH |
| | CIRCUITS WITH #8 AWG?? |
| | 210.11C3 (20A #12). |
| | |
| | 12) NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCULATIONS AND REQUIRED METHOD TO BE |
| | SHOWN. |
| | 215.5,106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE FS 553.80(2)(B) |
| | WITH RESPECT TO REPEAT COMMENTS. |
| | PLEASE KNOW, THIS IS ONLY NOTICE GIVEN |
| | AT THIS TIME. |
| | ** PLEASE KNOW, TWO "E" SHEETS ARE BEING |
| | RETAINED FOR FILE. |
| | |
| | ** PLEASE KNOW, THE NOTES ABOVE HAVE NO |
| | WAY SPECIFICALLY NOTED EVERY ITEM NOT |
| | CORRECT, HOWEVER ALL CODES HAVE BEEN |
| | GIVEN FOR ITEMS WHICH ARE NOT CORRECT ON |
| | PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |