| Plan Review Notes For Permit 06040145 |
| Permit Number |
06040145 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-20 00:00:00 | *** DENIED *** | | | 1) PROVIDE TWO COPYS OF THE ENERGY | | | CALCULATIONS. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT. | | | | | | 3) ENERGY CALCULATIONS ARE CALLING FOR 5 | | | KW HEAT, THE PLANS ARE CALLING FOR 10 KW | | | HEAT, THE TWO MUST COINCIDE PLEASE | | | CORRECT. | | | | | | 4) PLEASE SHOW THE SIZES OF ALL A/C | | | DUCTS ON MECHANICAL PLANS. | | | | | | 5) PLEASE SHOW MEANS AND SIZE OF RETURN | | | AIR TO AHU. | | | | | | 6) PROVIDE RETURN AIR FOR FAMILY ROOM, | | | PER 2004 FBC/R M1602.4 . | | | | | | 7) MASTER BATHROOM REQUIRES AN EXHAUST | | | FAN FOR TUB & SHOWER AREA, PER 2004 | | | FBC/R M1506 . | | | | | | 8) PLEASE SHOW THE LOCATION OF THE | | | CONDENSER UNIT ON THE MECHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|