Plan Review Notes
Plan Review Notes For Permit 06040145
Permit Number 06040145
Review Stop M
Sequence Number 1
Notes
Date Text
2006-04-20 00:00:00*** DENIED ***
 1) PROVIDE TWO COPYS OF THE ENERGY
 CALCULATIONS.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 3) ENERGY CALCULATIONS ARE CALLING FOR 5
 KW HEAT, THE PLANS ARE CALLING FOR 10 KW
 HEAT, THE TWO MUST COINCIDE PLEASE
 CORRECT.
  
 4) PLEASE SHOW THE SIZES OF ALL A/C
 DUCTS ON MECHANICAL PLANS.
  
 5) PLEASE SHOW MEANS AND SIZE OF RETURN
 AIR TO AHU.
  
 6) PROVIDE RETURN AIR FOR FAMILY ROOM,
 PER 2004 FBC/R M1602.4 .
  
 7) MASTER BATHROOM REQUIRES AN EXHAUST
 FAN FOR TUB & SHOWER AREA, PER 2004
 FBC/R M1506 .
  
 8) PLEASE SHOW THE LOCATION OF THE
 CONDENSER UNIT ON THE MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.