| Date |
Text |
| 2006-04-18 00:00:00 | |
| | FAILED |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE INDICATE THE LOCATION OF THE |
| | NEW SERVICE ON THE PLAN. SHOW THE |
| | LOCATION OF THE PANEL AND HOW FED FROM |
| | THE METER.INDICATE IF A DISCONNECT IS TO |
| | BE USED. |
| | |
| | 2} THE 2/0 FEEDER CONDUCTORS DO NOT |
| | COMPLY WITH 310.15(B)(6) FOR A 225 AMP |
| | SERVICE.. |
| | |
| | 3} PROVIDE THE FAULT CURRENT RATING FOR |
| | THE SERVICE EQUIPMENT PER 110.9 & 10. |
| | |
| | 4} PLEASE SEE THE WASHER AND DRYER |
| | WATTAGES ARE TOO LARGE IN THE |
| | CALCULATIONS AND DO NOT CORRELATE TO THE |
| | PANEL SCHEDULE. |
| | |
| | 5} THE SMALL APPLIANCES IN THE CALC DO |
| | NOT COMPLY WITH 220.16(A), 1500VA EACH, |
| | AND DO NOT CORRELATE WITH THREE SHOWN ON |
| | THE SCHEDULE. |
| | |
| | 6) THERE IS AN ERROR ON CIRCUIT #26 @ 40 |
| | AMPS ON A #12 CONDUCTOR. SEE 310.16. |
| | |
| | 7} PLEASE CLARIFY THE AIR HANDLER |
| | MOUNTING IN THE MASTER BEDROOM. IS IT IN |
| | AN ATTIC SPACE, AN DIF SO SHOW |
| | COMPLIANCE WITH THE REQUIRED LIGHT AND |
| | RECEPTACLE REQUIRED BY ARTICLES 210.70 |
| | AND 210.63. |
| | |
| | 8} A RECEPTACLE SHOULD BE ADDED BETWEEN |
| | OPENINS, EXISTING AND NEW, IN THE FAMILY |
| | ROOM EAST WALL, IF IT IS 2' OR MORE PER |
| | 210.52(A)(2), SEE REVIEWED PLAN. |
| | |
| | 9} THE RANGE IN THE CALCULATIONS IS NOT |
| | LISTED ON THE PANEL SCHEDULE. |
| | |
| | 10} THE ARC FAULT CIRCUITS REQUIRED BY |
| | 210.12 ARE NOT SHOWN ON THE PANEL |
| | SCHEDULE. |
| | |
| | 11} THE 20 AMP BATH CIRCUIT REQUIRED PER |
| | 210.11(C)(3) IS NOT ON THE PANEL |
| | SCHEDULE. |
| | |
| | 12} THE WHIRLPOOL TUB IN THE MASTER BATH |
| | MUST BE PROTECTED BY A GFI PER |
| | 680.62(A). |
| | |
| | 13 THE WATER PUMP AND IRRIGATION PUMP IN |
| | THE LOAD CALCULATION ARE NOT LISTED ON |
| | THE PANEL SCHEDULE |
| | |
| | PLEASE COORDINATE THE APPLIANCES |
| | ACTUALLY INSTALLED OR TO BE INSTALLED |
| | WITH THE CONTRACTORS PRIOR TO |
| | RESUBMITTING, AND INDICATE SAME ON BOTH |
| | LOAD CALCS PER ARTICLE 220, AN DON THE |
| | SCHEDULE PER ARTICLE 106.3.5.4-8 FBC AS |
| | AMMENDED BY THE CITY OF WEST PALM BEACH. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |