Plan Review Notes
Plan Review Notes For Permit 06040145
Permit Number 06040145
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-18 00:00:00 
 FAILED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 NEW SERVICE ON THE PLAN. SHOW THE
 LOCATION OF THE PANEL AND HOW FED FROM
 THE METER.INDICATE IF A DISCONNECT IS TO
 BE USED.
  
 2} THE 2/0 FEEDER CONDUCTORS DO NOT
 COMPLY WITH 310.15(B)(6) FOR A 225 AMP
 SERVICE..
  
 3} PROVIDE THE FAULT CURRENT RATING FOR
 THE SERVICE EQUIPMENT PER 110.9 & 10.
  
 4} PLEASE SEE THE WASHER AND DRYER
 WATTAGES ARE TOO LARGE IN THE
 CALCULATIONS AND DO NOT CORRELATE TO THE
 PANEL SCHEDULE.
  
 5} THE SMALL APPLIANCES IN THE CALC DO
 NOT COMPLY WITH 220.16(A), 1500VA EACH,
 AND DO NOT CORRELATE WITH THREE SHOWN ON
 THE SCHEDULE.
  
 6) THERE IS AN ERROR ON CIRCUIT #26 @ 40
 AMPS ON A #12 CONDUCTOR. SEE 310.16.
  
 7} PLEASE CLARIFY THE AIR HANDLER
 MOUNTING IN THE MASTER BEDROOM. IS IT IN
 AN ATTIC SPACE, AN DIF SO SHOW
 COMPLIANCE WITH THE REQUIRED LIGHT AND
 RECEPTACLE REQUIRED BY ARTICLES 210.70
 AND 210.63.
  
 8} A RECEPTACLE SHOULD BE ADDED BETWEEN
 OPENINS, EXISTING AND NEW, IN THE FAMILY
 ROOM EAST WALL, IF IT IS 2' OR MORE PER
 210.52(A)(2), SEE REVIEWED PLAN.
  
 9} THE RANGE IN THE CALCULATIONS IS NOT
 LISTED ON THE PANEL SCHEDULE.
  
 10} THE ARC FAULT CIRCUITS REQUIRED BY
 210.12 ARE NOT SHOWN ON THE PANEL
 SCHEDULE.
  
 11} THE 20 AMP BATH CIRCUIT REQUIRED PER
 210.11(C)(3) IS NOT ON THE PANEL
 SCHEDULE.
  
 12} THE WHIRLPOOL TUB IN THE MASTER BATH
 MUST BE PROTECTED BY A GFI PER
 680.62(A).
  
 13 THE WATER PUMP AND IRRIGATION PUMP IN
 THE LOAD CALCULATION ARE NOT LISTED ON
 THE PANEL SCHEDULE
  
 PLEASE COORDINATE THE APPLIANCES
 ACTUALLY INSTALLED OR TO BE INSTALLED
 WITH THE CONTRACTORS PRIOR TO
 RESUBMITTING, AND INDICATE SAME ON BOTH
 LOAD CALCS PER ARTICLE 220, AN DON THE
 SCHEDULE PER ARTICLE 106.3.5.4-8 FBC AS
 AMMENDED BY THE CITY OF WEST PALM BEACH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved