2006-05-22 00:00:00 
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 FEFFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES. WPB
 AMENDMENTS 108.3
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THESE
 INCLUDE WINDOWS/DOORS/ALL ROOFING
 MATERIALS/GLASS BLOCK AND
 CONNECTORS.VENTILATION
  
 5) R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR
 EACH SEPARATE SPACE BY VENTILATING
 OPENINGS PROTECTED AGAINST THE ENTRANCE
 OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE
 MESH, WIT H 1 / 8 INCH (3.2 MM) MINIMUM
 TO 1/4 INCH (6.4 MM) MAXIMUM OPENINGS.
  
 6) TRUSS DESIGN
 R802.10.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SECTION R802.10.1 ,
 SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS
 SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS
 DESIGN DRAWING SHALL BE PROVIDED WITH
 THE SHIPMENT OF TRUSSES DELIVERED TO THE
 JOBSITE.
  
 7) R802.10.2 DESIGN .
 WOOD TRUSSES SHALL BE DESIGNED IN
 ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICE. THE DESIGN AND MANUFACTURE OF
 METAL PLATE CONNECTED WOOD TRUSSES SHALL
 COMPLY WITH ANSI/TPI 1. THE TRUSS DESIGN
 DRAWINGS SHALL BE PREPARED BY A
 REGISTERED PROFESSIONAL WHERE REQUIRED
 BY THE STATUTES OF THE JURISDICTION IN
 WHICH THE PROJECT IS TO BE CONSTRUCTED
 IN ACCORDANCE WITH SECTION R106.1.
  
 8) SHOW IN DETAIL HOW THE AIR/HU WILL
 WILL BE INSTALLED IN THE ATTIC.
  
 9) R613.6.2 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE. WHERE THE WOOD
 SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR
 ASSEMBLIES SHALL BE ANCHORED THROUGH THE
 MAIN FRAME OR BY JAMB CLIP OR SUBFRAME
 SYSTEM, IN ACCORDANCE WITH
 THE MANUFACTURERS PUBLISHED INSTALLATION
 INSTRUCTIONS. ANCHORS SHALL BE SECURELY
 FASTENED DIRECTLY INTO THE MASONRY,
 CONCRETE OR OTHER STRUCTURAL SUBSTRATE
 MATERIAL. UNLESS OTHERWISE TESTED, BUCKS
 SHALL EXTEND BEYOND THE INTERIOR FACE OF
 THE WINDOW OR DOOR FRAME SUCH THAT FULL
 SUPPORT OF THE FRAME IS PROVIDED.
  
 10) 1506.3 VENTILATION RATE.
 VENTILATION SYSTEMS SHALL BE DESIGNED TO
 HAVE THE CAPACITY TO EXHAUST THE MINIMUM
 AIR FLOW RATE DETERMINED IN ACCORDANCE
 WITH TABLE M1506.3 .
  
 11) NOTE: ALL MATERIALS AROUND MOISTURE
 AREAS SHALL BE MOISTURE RETARDANT.
 SEE. R319 AND R320 FOR MORE INFORMATION
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  