2006-04-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.PLEASE KEEP THE
 NOC PROVIDED IN THE PACKAGE.
  
 2.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING FIRM IS
 REQUIRED TO BE ON THE PLAN,
 FAC61G15-23.002.
  
 3.)THE ENGINEER'S SEAL IS EXPIRED.IT
 IS TO STATE "LICENSE", NOT
 "CERTIFICATE", FAC61G15-23.ALSO SEE
 THE FPBE WEBSITE, WWW.FBPE.ORG.
  
 4.) REVISE THE PROJECT DESCRIPTION ON
 THE APPLICATION.REFERRING TO ANOTHER
 DOCUMENT IS NOT A DESCRIPTION OF THE
 PROJECT.
  
 5.)SEE ATTACHED POLICY IN REGARDS TO
 INFORMATION REQUIRED FOR REROOF PERMITS.
 INCLUDE ALL REQUIRED INFORMATION ON THE
 PROJECT DESCRIPTION.
  
 6.)YOUR PROJECT DESCRIPTION REFERS TO
 SPECIFICATIONS, THE SPECIFICATION REFERS
 TO THE CONDO ASSOCIATION AS THE JOB
 LOCATION.THE NOC
 REFERS TO CLUBHOUSE REPAIRS.THERE IS
 NOTHING ON EITHER THE APPLICATION OR THE
 ENGINEERING INDICATING THE BUILDING YOU
 ARE WORKING ON.PLEASE CLARIFY.
  
 7.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING CONDITIONS.IS FIRE
 RESISTANCE REQUIRED BASED ON BUILDING
 TYPE?FIRE RESISTANCE INFORMATION WAS
 PROVIDED BUT DESIGN CRITERIA WAS NOT
 GIVEN.CODE COMPLIANCE CANNOT BE
 DETERMINED DUE TO INSUFFICIENT
 INFORMATION.
  
 8.)THE ENGINEER HAS SPECIFIED 110PSF
 AS THE DESIGN PRESSURE.HE HAS
 SPECIFIED METAL ROOFING PANELS WHICH
 HAVE A DESIGN PRESSURE LIMITATION OF
 -41.5PSF, ENHANCED FASTENING NOT ALLOWED
 FOR FIELD OR PERMETER ZONES ACCORDING TO
 PRODUCT LIMITATION #1 OF THE NOA.
 ADDRESS.
  
 9.)THE SPECIFICATION STATES TO REMOVE
 THE DAMAGED WOODEN SOFFIT TRUSS MEMBERS,
 THEN CONSTRUCT NEW METAL TRUSS MEMBERS
 TO SUPPORT THE NEW DENSGLASS SOFFIT.
 YOUR DRAWING SHOWS STEEL STUDS IN THE
 SOFFIT AREA, SIDE ELEVATION.CLARIFY
 SCOPE OF WORK.IT APPEARS THAT YOU ARE
 REMOVING THE EXISTING WOOD SOFFIT
 FRAMING, REBUILDING WITH STEEL FRAMING?
 ARE YOU REPLACING ONLY THE ONES WHICH
 ARE DAMAGED AS STATED, OR REBUILDING
 EVERYTHING?IF YOU ARE REPLACING ONLY
 DAMAGED WOOD (WITH STEEL), PROVIDE A
 SPECIFICATION FOR FASTENING OF THE
 DENSGLASS INTO WOOD.ONLY A STEEL
 DETAIL SHOWN.
  
 10.) THE SPECIFICATION STATES THAT THIS
 IS A WOOD DECK, AND THAT YOU ARE
 REPAIRING ROTTED AREAS OF THE WOOD DECK.
 THERE IS NO MENTION OF USING DENSDECK,
 OR A FASTENING SPECIFICATION, BUT YOU
 HAVE INCLUDED THE SPECIFICATION SHEET
 FOR DENSDECK.CLARIFY SCOPE OF WORK.
  
 11.)SPECIFY DESIGN CRITERIA (WIND) FOR
 THE SOFFIT, FBC16.
  
 12.)THE SIDE SECTION DETAIL DOES NOT
 SHOW A PITCHED ROOF.IT SHOWS A FLAT
 DECK.THE FRONT ELEVATION SHOWS WHAT
 APPEARS TO BE A PITCHED ROOF.NO ROOF
 PITCH IS SPECIFIED ON EITHER THE
 APPLICATION, SPECIFICATIONS, OR THE
 PLAN.YOU ARE REMOVING A BUILT UP ROOF,
 IMPLYING A FLAT DECK, BUT INSTALLING A
 METAL ROOF, IMPLYING A PITCHED ROOF.
 CLARIFY SCOPE OF WORK AND SITE
 CONDITIONS.
  
 13.)THE DETAIL ON THE TOP LEFT IS
 CONFUSING.YOU SPECIFY TWO FASTENERS,
 ONLY ONE IS SHOWN.IT APPEARS TO BE
 SHOWING TWO DIFFERENT ATTACHMENTS,
 SHOWING THEM ADJACENT, BUT THEY ARE NOT
 ADJACENT (ONE AT THE BEAM, THE OTHER AT
 THE END OF THE OVERHANG, 4FT AWAY).IT
 IS NOT CLEAR WHY THIS EXPLODED DETAIL IS
 SHOWN, ESPECIALLY AS IT DIFFERS FROM
 BOTH ATTACHMENTS AND SHOWS ONLY ONE
 FASTENER WHERE THE TEXT AND OTHER
 GRAPHIC SHOWS TWO.
  
 14.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 IF A STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 PRODUCT APPROVAL WILL BE ISSUED.