Plan Review Notes
Plan Review Notes For Permit 06040142
Permit Number 06040142
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-27 00:00:00 
  
 DENIED
  
 1) THE OWNER OF A UNIT/CONDO CANNOT PULL
 AN OWNER/BUILDER PERMIT. THIS OPTION IS
 FOR WORK UNDER 25,000 IF YOU OWN THE
 BUILDING.ALL WORK SHALL BE PERFORMED BY
 A LICENCED CONTRACTOR
  
 2) PROVIDE OCCUPANCY AND CONSTRUTION
 TYPE OF THE BUILDING
  
 3) IF BUILDING IS SPRINKLERED THE SPACE
 UNDER THE MEZZANINE IS REQUIRED TO ALSO
 PER 505.5.2 FBC
  
 4) STRUCTURAL CALCULATIONS PROVIDED HAVE
 AN OUTDATED SEAL, PERMIT APPLICATIONS
 SUBMITTED AFTER DEC. 31, 2005 REQUIRE
 THE NEW SEALS PER 61G15-23.001(1) F.A.C.
 SUBMIT 2 SIGNED AND SEALED COPIES
  
 5) ALONG WITH CALC'S AN AFFIDAVIT BY THE
 ENGINEER STATING THE SAFE ALLOWABLE
 FLOOR LOAD IN POUNDS PER SQUARE FOOT
 SHALL BE SUBMITTED PER 110.4.2 FBC*
  
 6) THE OWNER SHALL POST A SIGN WITH THE
 SAFE ALLOWABLE LOAD STATED IN A
 CONSPICUOUS PLACE PER 110.4.3 FBC*
  
 7) PROVIDE A FLOOR PLAN OF THE UNIT
 SHOWING THE DIMENSIONS AND ANY BUILDOUT
 IN THE UNIT. NO ENCLOSED SPACES CAN BE
 BUILT UNDER THE PROPOSED MEZZANINE, AS
 THE SIZE OF MEZZANINE CORESPONDS
 DIRCETLY TO THE OPEN FLOOR SPACE PER
 505.2 FBC
  
 8) CLARIFY THAT THE CLEAR HEIGHT
 SPECIFIED ON DRAWINGS IS ABOVE MEZZANINE
 FLOOR
  
 9) PROVIDE STAIR RISER HEIGHT AND NUMBER
 OF RISERS, MAX. RISER HT. 7" PER 1009.3
  
 10) ELECTRICAL ABOVE OR BELOW MEZZANINE
 WILL REQUIRE A SEPERATE PERMIT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  