| Date |
Text |
| 2006-04-27 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) THE OWNER OF A UNIT/CONDO CANNOT PULL |
| | AN OWNER/BUILDER PERMIT. THIS OPTION IS |
| | FOR WORK UNDER 25,000 IF YOU OWN THE |
| | BUILDING.ALL WORK SHALL BE PERFORMED BY |
| | A LICENCED CONTRACTOR |
| | |
| | 2) PROVIDE OCCUPANCY AND CONSTRUTION |
| | TYPE OF THE BUILDING |
| | |
| | 3) IF BUILDING IS SPRINKLERED THE SPACE |
| | UNDER THE MEZZANINE IS REQUIRED TO ALSO |
| | PER 505.5.2 FBC |
| | |
| | 4) STRUCTURAL CALCULATIONS PROVIDED HAVE |
| | AN OUTDATED SEAL, PERMIT APPLICATIONS |
| | SUBMITTED AFTER DEC. 31, 2005 REQUIRE |
| | THE NEW SEALS PER 61G15-23.001(1) F.A.C. |
| | SUBMIT 2 SIGNED AND SEALED COPIES |
| | |
| | 5) ALONG WITH CALC'S AN AFFIDAVIT BY THE |
| | ENGINEER STATING THE SAFE ALLOWABLE |
| | FLOOR LOAD IN POUNDS PER SQUARE FOOT |
| | SHALL BE SUBMITTED PER 110.4.2 FBC* |
| | |
| | 6) THE OWNER SHALL POST A SIGN WITH THE |
| | SAFE ALLOWABLE LOAD STATED IN A |
| | CONSPICUOUS PLACE PER 110.4.3 FBC* |
| | |
| | 7) PROVIDE A FLOOR PLAN OF THE UNIT |
| | SHOWING THE DIMENSIONS AND ANY BUILDOUT |
| | IN THE UNIT. NO ENCLOSED SPACES CAN BE |
| | BUILT UNDER THE PROPOSED MEZZANINE, AS |
| | THE SIZE OF MEZZANINE CORESPONDS |
| | DIRCETLY TO THE OPEN FLOOR SPACE PER |
| | 505.2 FBC |
| | |
| | 8) CLARIFY THAT THE CLEAR HEIGHT |
| | SPECIFIED ON DRAWINGS IS ABOVE MEZZANINE |
| | FLOOR |
| | |
| | 9) PROVIDE STAIR RISER HEIGHT AND NUMBER |
| | OF RISERS, MAX. RISER HT. 7" PER 1009.3 |
| | |
| | 10) ELECTRICAL ABOVE OR BELOW MEZZANINE |
| | WILL REQUIRE A SEPERATE PERMIT |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |